Periphery board (500p) FCI2017
Description
2
26 | 46
Building Technologies
A6V10315038_f_en_--
Siemens Industry, Inc.
2016-02-25
Properties
●
Two different power supplies can be connected:
– Power supply (170 W) FP2011 only for fire control panels with a maximum load
of 6.5 A
– Power supply (300 W) FP2012 for fire control panels and voice alarm fire
control panels with a maximum loading of 11.5 A
– Power supply (300 W) FP2012 for voice alarm fire control panels in housings
(3HU) with a maximum loading of 22 A
●
Battery charger capable of charging up to 100 Ah batteries at a maximum of 6 A.
●
Power supply (300W) FP2012 must be used for batteries of more than 33 Ah.
●
Power supply (170W) FP2011 must be used for batteries of 33 Ah or less.
●
Ground faults detected at <1 k
Ω
to ground.
●
Ground fault detection for all circuits except the 2 detector circuits handled by PMI.
Each detector core has its own ground fault and supervision circuit.
●
Two integrated FDnet/C-NET circuit cards, one for circuits 1 and 2 and one for
circuits 3 and 4, and EMC surge protection for eight style 4 or four style 6 circuits.
●
Maximum of 252 device addresses can be controlled per integrated FDnet/C-NET
circuit card.
●
Three relay outputs and one user programmable relay output for common alarm,
common trouble, common supervision, and user programmable.
●
The auxiliary output is a regulated DC 24 V output with a maximum of 1.5 A.
●
Degraded alarm and trouble mode functions when either or both CPUs for the
periphery board or PMI are compromised.
●
Integrated NAC circuits, specified for DC 24 V, configured for either one class A
(style Z) or two class B (style Y) circuits, with a maximum of 3 A for one class A or
max. 3 A for each of the two class B circuits. NACs have integrated
synchronization protocol for audible or visual notification appliances.
– All NAC circuits are supervised and protected for overcurrent and direct short-
circuited output.
●
Two slots for optional extensions, one of which is for NAC module (1A/2B) or
releasing module (XCI2001):
– NAC module (1A/2B) FCI2001 for one additional class A circuit or two class B
circuits (same data as integrated NAC circuits) (P/N S54400-A54-A1). The
module connects to X901.
– Releasing module (XCI2001) (P/N S54400-A69-A1) The module connects to
X901.
– Leased line or city tie module FCI2020 (P/N 54400-A57-A1). The module
connects to X902.
●
Additional peripheral data bus connection (X202) for LED or DACT modules.
●
Main CPU and detector core CPUs capable of being updated in the field through
the PMI.