Periphery board (500p) FCI2017
Views
2
29 | 46
Building Technologies
A6V10315038_f_en_--
Siemens Industry, Inc.
2016-02-25
Element
Des.
Function
Jumpers
X403
DEGRADE ALARM SILENCEABLE/NONSILENCEABLE
X602
DEGRADED MODE ENABLE/DISABLE for NAC 1 class A or NAC 1-1 class B
X603
DEGRADED MODE ENABLE/DISABLE for NAC 1-2 class B
X604
NAC 1 class A/B selection
X605
NAC 1 class A/B selection
X606
NAC 1 class A/B selection
X305
Power supply 2 ON/OFF
Connector
X201
PMI & mainboard bus
X202
Peripheral data bus output
X204
Future expansion
X301
Connector for power supply 1 (PS1)
X302
Connector plug for power supply 2 (PS2) in housing (3HU)
X303
Battery connection
X304
DC 24 V connection to Card Cage VCA2002 for feed to the voice alarm modules and
associated peripherals
X601
NAC1 output
X801
Bell follower input
X901
NAC 2 expansion or releasing module
X902
Leased line / city tie module
X1001
Auxiliary DC 24 V output
X1101
Common alarm relay positions 1…3
Common trouble relay positions 4…6
Common supervisory relay positions 7…9
User programmable relay positions 10…12
X1302
For future applications
X1401
Detector circuit core A, circuit 1
X1402
Detector circuit core A, circuit 2
X1702
For future applications
X1801
Detector circuit core B, circuit 3
X1802
Detector circuit core B, circuit 4