Scenario 2 – Must/Can
Alarm Event is set to Must Report on Account 1 and Can
Report on Account 2. Panel fails on Account 1 the first
time.
Step 1:
Panel goes into alarm.
Step 2:
Panel tries to send event
to Account 1, but is
unsuccessful.
N
Account 1
Account 2
Step 3:
Panel keeps trying to send event to Account 1 until the programmed Number
Of Attempts has been reached.
Step 4:
Panel switches to Account
2 and attempts to transmit,
but is unsuccessful too.
N
Account 1
Account 2
Step 5:
Panel keeps trying to send event to Account 2 until the programmed Number
Of Attempts has been reached.
Done.