18 – 28VDC for battery
Current: Max. 0.4A
Supervised
Output:
City Tie-Output 1
Normal output voltage: 19-28VDC (open circuit condition)
Supervisory current: 1mA
Maximum trip current: 400mA
Maximum coil plus wire resistance:
22.5Ω
Leased line-Output 1
Normal output voltage:
19-28VDC (open circuit condition)
Trouble output voltage:
0V
Alarm output voltage:
-(19-28)VDC (open circuit condition)
Maximum wire resistance:
2-
5KΩ
Maximum short circuit current:
25mA
Leased line-Output 2
Normal output voltage:
19-28VDC (open circuit condition)
Supervisory output voltage:
-(19-28)VDC (open circuit condition)
Maximum wire resistance:
2-
5KΩ
Maximum short circuit current:
25mA
DACT Circuits
Power limited
Supervised for short or open circuit conditions
Compliance to FCC part 68
Support RJ31X connection
Compatible Digital Alarm Communication Receiver (DACR) list,
Device Module
Manufacture
MX8000
Honeywell
CAUTION:
– To reduce the risk of fire, use only No. 26 AWG or larger telecommunication line cord.
Only to a loop start telephone circuit and not to a ground start telephone circuit.
To verify the integrity of the call forwarding feature every 24 hours.