NAC Wiring
Two individual NACs are provided and the polarity shown is when the NAC is activated.
Power Limited
Supervised
Current Draw
Maximum Line Resistance
2.5A
3.2
Ω
2.0A
4.0
Ω
1.5A
5.3
Ω
1.0A
8.0
Ω
0.5A
16.0
Ω
Alarm voltage: 16 to 32VDC
Maximum ripple: 0.1VAC
Used for special application only
Two Style Y/Class B or one Style Z/Class A
Total maximum current: 2.5A
Refer to Cerberus Pro_NACs_A6V10333532_c_en to determine synchronized notification
appliances allowed per NAC
Style Y, Class B
Supervised
Power Limited
See Appendix B for compatible devices
EOL available in the package as part of accessory
24K 0.5W
resistor*
…..
N_AN
N_AP
N_BN
NAC
N_BP
Same as above
Style Z, Class A
Supervised
Power Limited
See Appendix B for compatible devices
No EOL devices
…..
N_AN
N_AP
N_BN
NAC
N_BP
38