SYSTEM WIRING
Before connecting the field wiring, check the wiring for opens, shorts, grounds and stray
voltages.
WARNING
Damage may result if a high voltage insulation tester is used on wiring while connected to the
control panel.
Terminate the field wiring to the main board in accordance with the diagrams in System Wiring
Section.
All wiring must be in accordance with local codes and the National Electrical Code.
AC Connection
Wire the AC supply to power supply on the back of enclosure. The supply should originate
from a dedicated 15A (minimum) branch circuit. It should be provided with a breaker or other
means of isolation that must be colored red.
Observe the wiring order — the top terminal is ground and must be wired back to the electrical
panel ground (earth) bonding point or another good ground acceptable to the authority having
jurisdiction and the electrical inspector. The neutral wire must be taken back to the electrical
panel neutral distribution bar.
Battery Connection
WARNING
Improper battery connections or shorting battery terminals may damage the system
and/or batteries and may cause personal injuries.
The control panel uses a 24V battery set. Connect the two 12V batteries in series with
provided wire. Route the battery leads to the battery connector at bottom of the main board.
The battery leads are not power-limited.
DO NOT CONNECT BATTERIES YET.
WIRING
Basic system wiring and detector locations must be in accordance with NFPA 72 or other
instructions from the appropriate local authority having jurisdiction.
Devices that may be satisfactorily used with the control panel are shown in the compatible
device listing in Appendix B.
Wire reference data are included in Appendix A.
32