Installation
Connectable C-NET devices
5
35 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
Device type
Type
Description
↑ AI
Ext. AI
DBS 720
Neural radio fire
detector (SWING)
FDOOT271
Optical-thermal fire detector with radio
transmission to the radio gateway
FDCW241
1
X
X
–
Radio manual call
point (SWING)
FDM273
Indirect activation via radio gateway
FDCW241
X
–
–
FDM275
SWING manual call point, activation via
radio gateway FDCW241
X
–
–
Aspirating smoke
detector
VLF
VESDA LaserFocus (laser monitoring)
–
–
–
Table 1: Devices which can be connected to the C-NET detector line
X
Possible / available
–
Not possible / not available
1
Availability is communicated with the delivery release
2
Check with your country representative that this detector is approved for
C-NET in your country.
Most devices are supplied via the detector line.
The input/output module FDCIO223 must have an external power supply.
All ↑ C-NET devices have an integrated line separator.
NOTICE
Influencing the earth fault monitoring
Faults
● For devices on the C-NET with a separate supply, the supply must be
electrically isolated. FDCIO223 is an exception to this rule.
The number of connectable devices depends on the specific AK, RK, MK
connection factor of the type and is calculated using the 'Quantities Tool' software.
Note the specifications of the individual C-NET devices in the 'List of Compatibility'
document, see 'Applicable documents' chapter.
See also
1
C-NET detector line [➙ 31]