Testing the installation
Checking functions
8
59 | 62
Building Technologies
A6V10211094_f_en_--
Fire Safety
2015-12-15
8 Testing the installation
The fire detection installation can be switched to 'Test' operation mode to check it
is functioning properly.
8.1 Checking functions
The table below shows the recommended intervals for checking functions. National
specifications always take priority.
For details of the function test, refer to the 'Applicable documents' chapter.
Function
Activity
Interval
(years)
1 2 5
Software
Check date and time.
X
Detector lines:
● C-NET
Trigger an automatic detector and a manual call point per line.
X
Trigger all manual call points
X
Trigger all automatic fire detectors.
X
Check all detectors for soiling and application.
X
Check the function of the input/output modules.
X
On each line check whether short-circuit / open line triggers a 'Fault'.
Check the loop line function.
During short-circuit also check the separator function.
X
Fire controls
Check activation of the controls up to and with the interface.
X
Check isolations carried out by the customer. Arrange a time with the
customer.
X
Degraded function
X
Mains failure
Check 'Delayed for in case of a mains failure' function.
Alarm organization
Check the function of the delay times t1 and t2.
X
Alarm activation by automatic detector on 'unmanned'
⇒ Global alarm.
X
Alarm activation by manual call point on 'manned' and 'unmanned'
⇒ Local alarm/global alarm.
X
Check automatic switchover 'Manned' / 'Unmanned' on the basis of
the event memory entry.
X
Check activation of the remote transmission equipment with 'Alarm'. X
Actuate the corresponding danger level by activating a detector with
the detector exchanger and tester
X
Alarm devices
In emergency power operation check all alarm devices taking the
event category into account:
'Pre-alarm'
'Alarm'
'Fault'
X