18 / 22
Siemens
Desigo Touch and Web
CM111029en_04
Building Technologies
Compatibility & limitations – System limits
2014-08-15
2.5.4 Supported BACnet objects
Text #
Name
Type #
Description
0
DEV
8
Device
1
AI
0
Analog input
2
AVAL_OP
2
Analog value for operation
3
AO
1
Analog output
4
AVAL
2
Analog value
6
BI
3
Binary input
7
BVAL_OP
5
Binary value for operation
8
BO
4
Binary output
9
BVAL
5
Binary value
10
BSCHED
17
Binary scheduler
11
MI
13
Multistate input
12
MVAL_OP
19
Multistate value for operation
13
MO
14
Multistate output
14
MVAL
19
Multistate value
15
MSCHED
17
Multistate scheduler
16
CLN
6
Calendar
18
TRNDLOG
20
Trend log
19
CI
24
Counter input
20
CMD_CTL
216
Command Control
21
PWR_CTL
216
Power Control
22
AI_RED
0
Analog input, reduced function
23
AO_RED
1
Analog output, reduced function
24
BI_RED
3
Binary input, reduced function
25
BO_RED
4
Binary output, reduced function
26
MI_RED
13
Multistate input, red.function
27
MO_RED
14
Multistate output, red.function
31
CI_ACC
23
Counter input, accumulated
35
SCHED
17
Schedule*
50
USRPRF
207
User profile
58
Block
201
Block**
69
CMN_ALM
214
Common alarm
70
DevInfo
217
Device information for alarming
* no analog scheduler
** Block types are Desigo-specific
Note
MSCHED
MSCHED can have 6 different states, and 10 for
TREND
.
If more states exist, only the first 6 or 10 are displayed.
USRPRF
– The PXG3.W100 web interface supports user profiles with access level
≥ Extended Operation, allowing for resetting and confirming alarms.
– Read/write access rights to the BACnet object level are not processed.