20 / 22
Siemens
Desigo Touch and Web
CM111029en_04
Building Technologies
Compatibility & limitations – Firmware updates
2014-08-15
2.7 Firmware
updates
2.7.1 General
With the devices PXG3.W100 (all versions) and PXM40 / PXM50 (>1.15.30.497)
the firmware is updated in XWP using SSA-DNT; see E-learning module "Com-
missioning the web server". To ensure operation of the devices on the most current
firmware, the
current
firmware must be downloaded.
2.7.2 PXM
40/PXM50 ≤1.15.30.497
As a rule, the firmware of any PXM40/50s (referred to as “device”) can be updated
using the FWDT (Firmware Download Tool). This is particularly important if a FW
update is not possible via DNT (
D
iscovery and
N
ode Setup
T
ool) due to technical
issues. –
In devices with FW version ≤1.15.30.497, updating the firmware via FWDT
is
mandatory,
to be able to update the device using DNT in the future.
Procedure
1.
Disconnect
the device from power
.
2.
Press/hold
the
Reset
button,
reconnect
the device to power
.
3. Wait until the
orange LED flashes
(ca. 10 seconds), then
4.
release
the
Reset
button.
5.
Start
FWDT
.
6. Connect the device to the PC
via USB connection.
---> FWDT discovers the device and enters the mode specific to these devic-
es.
7. Group
box
Select the firmware version
> drop down list > select the accu-
rate firmware version for your device.
The
Select the firmware version
dropdown list will appear only if there’s
more than one firmware version available.
8. Click
Start Loading
.
---> FWDT starts uploading and displays a progress bar.