Siemens
Desigo Touch and Web
CM111029en_04
Building Technologies
Compatibility & limitations – System limits
2014-08-15
2.5.2.4 Connected web clients
Item
Limits
Description
Touch panel
10*
Max. number of touch panels per PXG3.W100 with overview page.
Web clients, max. system
design
3*
Max. number of registered users per PXG3.W100, where the limit of
permanently displayed BACnet objects of all clients may not be ex-
ceeded at maximum system design
1)
.
At low system design, more than 3 users can be logged in concurrent-
ly.
Example: 1 customized view at 3 graphics pages at 10 BACnet objects
each. If 10 web clients are connected to it, the system limit (300 per-
manently displayed BACnet objects) is reached.
All system limits must be adhered to simultaneously.
Limit*
Technical limit, tested.
Limit
Recommended limit, tested.
[Limit] Recommended limit, not tested.
·
20 customized views
·
5 graphics pages per customized view
·
20 BACnet objects per graphics page
ð
2000 BACnet objects total
ð
100 BACnet objects per customized view
·
3 Web clients with the above design
ð
300 permanently displayed BACnet objects
·
10 trends per customized view
·
10 schedulers per customized view
ð
Important: The configuration data size < 7MB applies to all of the above
1)
Example for max.
system design
ð
with system limits