Installation, Operation, and Maintenance Manual

CERBERUS PYROTRONICS™

PXL CONVENTIONAL FIRE ALARM CONTROL PANEL

Technical Manuals Online! - http://www.tech-man.com

firealarmresources.com

Содержание CERBERUS PYROTRONICS PXL

Страница 1: ...7932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN For PXL Firmware Revision 4 0 and higher Installation Operation and Maintenance Manual CERBERUS PYROTRONICS PXL CONVENTIONAL FIRE ALARM CONTROL PANEL Technical Manuals Online http www tech man com firealarmresources com ...

Страница 2: ...INSULATE ALL CABLE DRAIN WIRES from any conduit or earth grounded electrical box including those in the PXL enclosure 4 Connect shield cable drain wire ONLY inside the PXL enclosure CAUTIONS AND WARNINGS This caution symbol appears periodically throughout this manual It identifies important safety instructions Read these instructions care fully Failure to follow these instructions may result in da...

Страница 3: ... PMK 1 Bracket in the PSE 1 22 STEP 11 Install the PTX 12 23 STEP 12 Install Grounding Straps 24 STEP 13 Check Field Wiring 26 STEP 14 Install Field Wiring 26 Wiring to the PSE 1 Enclosure 26 Initiating Device Circuits 30 Notification Appliance Circuits 31 Wiring to the PCM 1 32 Wiring to the Optional PZE 4B Modules 32 Wiring to the PPS 10M 32 Wiring to the PNC 2Z 33 Wiring to the PRM 4 34 STEP 15...

Страница 4: ...erification Retard Reset Timer 45 Set Bell Codes 46 Set Country Code 46 Set Custom Messages 47 Set Global Relays 47 Set NAC Cutoff Timer 47 Set NAC Inhibit Timer 47 Set Passcodes 47 Set System ID 47 Test 47 Zone Types 48 Alarm Verification 48 Generic Zone 49 Reset Zone 49 5 Testing and Troubleshooting 53 WALK TEST 53 SYSTEM TEST 54 Every Six Months 54 Every Year 54 FUSE REPLACEMENT IN THE PXL SYST...

Страница 5: ...ling the PMK 1 Bracket in the PSE 1 22 17 Mounting the PTX 12 23 18 Installing the Grounding Strap with Two Lugs 24 19 Installing the Grounding Strap with One Lug 25 20 PXL Power Limited Wiring 28 21 The PCM 1 User Interface 35 22 PXL Automatic System Configuration Mode 40 23 PXL Normal Operating Mode 42 24 Line Graph of Alarm Verification 49 25 PPS 10M Wiring for Canadian Automatic Battery Discon...

Страница 6: ...PPS 10M 32 11 Wiring to the Optional PNC 2Z 33 12 Wiring to the Optional PRM 4 34 13 PXL Programming Options 51 14 PXL Fuse Replacement 55 15 Silent Knight Model 5128 5129 Programming Table 72 Illustrations Cont 26 Mounting the Silent Knight Model 5128 in a PXL Enclosure 70 27 PXL to Silent Knight Model 5128 5129 Wiring Diagram 71 28 Cabling Connections in a PSE 2 Enclosure with Full Module Capaci...

Страница 7: ...ts are included in the basic PXL Control Panel PCM 1 Main Control Board with 12 Initiating Device Circuits user controls PPS 10M Power Supply with 4 Notification Appliance Circuits 3 dedicated Form C relays PTX 12 Power Transformer PSE 1 Enclosure with PMK 1 Mounting Bracket Batteries which must be purchased separately that are capable of supplying all power necessary to operate the PXL and supply...

Страница 8: ...R O T R O N I C S P X L S Y S T E M N O R M A L M E N U 1 2 0 0 0 0 POWER ALARM SUPERVISORY TROUBLE AUDIBLES SILENCED PARTIAL DISABLE CERBERUS PYROTRONICS Figure 1 Basic PXL System Exterior View Interior View Technical Manuals Online http www tech man com firealarmresources com ...

Страница 9: ... system locally at the main control Batteries which must be purchased separately that are capable of supplying all power necessary to operate the PXL and supply 1 amp auxiliary 24 VDC and up to 10 amps of NAC current at 24 volts when in alarm NOTE Both the Auxiliary current and the NAC current together cannot exceed 10 Amps RSA DRIV RSA 16 Remote System annunciators and control units up to a maxim...

Страница 10: ...PXL Conventional Fire Alarm Control Panel Introduction 4 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 11: ...hnical Support Install and use the PXL System in accordance with the NEC and local electrical code requirements GENERAL GUIDELINES FOR PXL INSTALLATION WARNING Always remove power first battery and then AC and wait at least 10 seconds to allow the supply voltages to decay before installing or removing any module cable or wiring Follow Steps 1 through 16 for installation Each step is thoroughly exp...

Страница 12: ...dule 8 Plug in the power data interconnect cable from the PPS 10M board and from PCM 1 9 Install any optional PZE 4B zone expander modules Install interconnecting cables 10 Install the PMK 1 module bracket in the PSE 1 enclosure 11 Install the PTX 12 transformer 12 Install the grounding straps 13 Check field wiring 14 Install field wiring including the main power connections Refer to the PXL Conne...

Страница 13: ...l and manual access to the PCM 1 Display Panel Weight and size of enclosure Local mounting codes When mounting the PSE 1 position the backbox clear of obstruction so that the door can open freely and so that indicators and controls are easily accessible To Install the PSE 1 Enclosure 1 Slip the door off the hinges of the box and put it to one side temporarily Figure 2 The PSE 1 Enclosure Technical...

Страница 14: ...e against the wall at the designated height 5 Mark drill points on the wall in the center of the two slots on the upper rear of the box Refer to Figure 2 6 Drill the two holes and screw in the top bolts leaving a small gap between the wall and each top bolt 7 Mount the enclosure on the two bolts and then install the bottom bolts 8 Tighten all bolts securely against the back wall of the enclosure F...

Страница 15: ...gives reliable operation CAUTION The PPS 10M must be installed before mounting and wiring the PCM 1 Setting the Address Before mounting the PPS 10M to the PMK 1 bracket set the address on Switch S1 according to Table 1 Refer to Figure 4 for the location of S1 and to the Note that follows for the operation of the switches NOTE To open a dipswitch press down on the side of the dipswitch marked OPEN ...

Страница 16: ...f the bracket as shown in Figure 6 3 Fasten the board to the mounting bracket in three places using the screws provided See Figure 6 Figure 4 PPS 10M Module Board NOTES When two Model PPS 10M power supplies are used in a PXL System 1 Cut Jumper JP3 on the second PPS 10M 2 Disable TB5 on the second PPS 10M 3 Cut and remove the red wires from the 15 cable in the PCK 1 kit P N 500 695066 when connect...

Страница 17: ...XL Conventional Fire Alarm Control Panel 11 Figure 5 Sliding the PPS 10M into the PMK 1 Bracket Figure 6 Mounting the PPS 10M on the PMK 1 Bracket Technical Manuals Online http www tech man com firealarmresources com ...

Страница 18: ...1 according to Table 2 Refer to Figure 7 for the location of S1 and to the Note on page 9 for the operation of the switches TABLE 2 SETTING THE ADDRESS ON THE PRM 4 Module Number Relay Range Switch Setting 1 2 3 4 5 1 1 4 X O O O O 2 5 8 O X O O O 3 9 12 X X O O O 4 13 16 O O X O O 5 17 20 X O X O O 6 21 24 O X X O O 7 25 28 X X X O O 8 29 32 O O O X O X SWITCH CLOSED OR ON O SWITCH OPEN OR OFF Fi...

Страница 19: ... bracket next to the PPS 10M with the terminal blocks facing out and the locating tab protruding through the slot of the bracket as shown in Figure 8 2 Fasten the board to the mounting bracket with the screw provided See Figure 8 Figure 8 Mounting the PRM 4 on the PMK 1 Bracket Technical Manuals Online http www tech man com firealarmresources com ...

Страница 20: ...K 1 bracket set the address on Switch S1 according to Table 3 Refer to Figure 9 for the location of S1 and to the Note on page 9 for the operation of the switches X SWITCH CLOSED OR ON O SWITCH OPEN OR OFF Figure 9 PNC 2Z Module Board TABLE 3 SETTING THE ADDRESS ON THE PNC 2Z Module Number NAC Range Switch Setting 1 2 3 4 5 1 9 10 X O O O O 2 11 12 O X O O O 3 13 14 X X O O O 4 15 16 O O X O O Tec...

Страница 21: ... the terminal blocks facing out and the locating tab protruding through the slot of the bracket as shown in Figure 10 If the PRM 4 is not used place the PNC 2Z next to the PPS 10M 2 Fasten the board to the mounting bracket with the screw provided See Figure 10 Figure 10 Mounting the PNC 2Z on the PMK 1 Bracket Technical Manuals Online http www tech man com firealarmresources com ...

Страница 22: ...of the PCM 1 after that module is installed NOTE If the PRM 4 and PNC 2Z are not used in your system configuration no further connections are necessary at this time 2 Plug one end the power data cable P N 555 194066 shipped with the PRM 4 into JP1 of the PRM 4 and the other end into JP1 of the PPS 10M 3 Plug one end of the power data cable P N 555 194066 shipped with the PNC 2Z into JP1 of the PNC...

Страница 23: ... and with the locating pins protrud ing through the bottom of the bracket as shown in Figure 11 2 Fasten the PCM 1 to the mounting bracket at the positions marked A in Figure 11 using the screws provided 3 Remove the backing from the PCM 1 LED label and place it on the PCM 1 bezel Refer to Figure 11 4 a Complete the zone label for the zone overlay with the appropriate zone description Refer to Fig...

Страница 24: ...re Alarm Control Panel Installation 18 Figure 11 Mounting the PCM 1 on the PMK 1 Bracket Figure 12 Labeling the Zones and Terminal Blocks on the PCM 1 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 25: ...r to STEP 6 No 1 Plug the other end of the power data cable P N 555 194066 that was previously installed in the PPS 10M JP2 into the PCM 1 JP7 STEP 9 Install the Optional PZE 4B Setting the Address Before mounting the PZE 4B to the PMK 1 bracket set the address on Switch S1 according to Table 4 Refer to Figure 13 for the location of S1 and the Note on page 9 for the operation of the switches TABLE...

Страница 26: ...arm Control Panel Installation 20 Figure 13 PZE 4B Module Board Figure 14 Mounting the PZE 4B Figure 15 Labeling the Zones and Terminal Blocks on the PZE 4B Technical Manuals Online http www tech man com firealarmresources com ...

Страница 27: ...priate zone description Refer to Figure 15 For example Floor 1 East Wing Floor 1 West Wing Slip the label under the overlay so the information shows through b Fill in the terminal block label with the appropriate zone information 2 Place the bezel in the appropriate position on the PMK 1 mounting bracket Refer to Figure 14 Be sure that the locating pin on the bezel goes through the hole in the bra...

Страница 28: ...acket over the 4 studs in the upper portion of the PSE 1 enclosure Refer to Figure 16 for the location of the studs 2 Secure the bracket in place by using the 4 lock washers flat washers and nuts that were removed and placed to one side in STEP 1 No 2 Figure 16 Installing the PMK 1 Bracket in the PSE 1 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 29: ...e PTX 12 in the lower left corner of the PSE 1 enclosure with the studs from the cabinet protruding through the mounting bracket Refer to Figure 17 2 Secure the PTX 12 to the PSE 1 enclosure by placing the flat washers then the lock washers and finally the nuts over the studs 3 Tighten the nuts securely Figure 17 Mounting the PTX 12 Technical Manuals Online http www tech man com firealarmresources...

Страница 30: ...to Figure 18 a Using the 10 x 32 1 4 screw provided connect one end of the grounding strap to the standoff in the door of the PSE 1 b To connect the other end of the grounding strap remove only one 10 nut from the upper left corner stud stamped GROUND place the lug over the stud and then replace and tighten the 10 nut Figure 18 Installing the Grounding Strap with Two Lugs Technical Manuals Online ...

Страница 31: ...g to the PPS 10M TB1 6 ERG Make this connection after mounting the PPS 10M to the PMK 1 bracket b To connect the end of the grounding strap with the lug remove the 10 nut from the upper left corner stud stamped GROUND place the lug over the stud and then replace and tighten the 10 nut Figure 19 Installing the Grounding Strap with One Lug Technical Manuals Online http www tech man com firealarmreso...

Страница 32: ...odules and wiring to this control panel When installing power limited field wiring the installer must comply with NEC article 760 54 which states The fire alarm power limited circuits are installed using Types FPL FPLR FPLP or permitted substitute cable provided these power limited cable conductors extending beyond the jacket are separated by a minimum of 0 25 in 6 35 mm or by a nonconductive slee...

Страница 33: ...d Line open Incorrect EOLR value NAC device wired backward NAC device not polarized 3 Check for Notification Appliance Circuit Ground Fault Measure between F and ground 1 megohm Line shorted F and ground 1 megohm Line shorted 4 Measure Initiating Device Circuit Loop Resistance Remove the 3 9K End of Line Resistor and short end prior to measurement IDC with relay or audible base 40 ohms Line open I...

Страница 34: ...PXL Conventional Fire Alarm Control Panel Installation 28 Figure 20 PXL Power Limited Wiring Technical Manuals Online http www tech man com firealarmresources com ...

Страница 35: ... separate tie down to lances located on the rear of the enclosure See Figure 20 for the location of the lances WIRING ENTERING ENCLOSURE Power Limited Wiring Wiring to the following PXL module terminations is considered power limited and must enter the enclosure through the knockouts specified in Table 7 Refer to Figure 20 Wiring between the knockout speci fied and the module termination must be i...

Страница 36: ...91 linear beam smoke detector one relay base or audible base or remote alarm lamp 5 Each IDC if configured as an alarm verified zone is capable of distinguishing between a shorting type device and a smoke detector in alarm 6 Remote accessories can not be used on IDCs configured with alarm verification 7 Each IDC is user programmable Refer to the Programming section of the manual for further inform...

Страница 37: ... the National Electric Code or consult the manufacturer of the wire in question Notification Appliance Circuits PPS 10 TB4 1 The circuits on PPS 10 TB4 are for notification appliances only NFPA 72 Local 2 All wiring must be in accordance with local and national codes 3 All notification appliance circuits are power limited to NFPA 70 and NEC 4 Electrical ratings Supervisory 24 VDC nominal 2 4mA max...

Страница 38: ... Refer to Table 9 Dress the field wiring that will be going to the PZE 4B terminals Strip the insulation from the wiring and connect the wires to the appropriate screw terminals TABLE 9 WIRING TO THE PZE 4B Screw Terminal Application TB1 1 4 2 Initiating Device Circuits TB2 1 4 2 Initiating Device Circuits Wiring to the PPS 10M Refer to Table 10 Dress the field wiring that will be going to the PPS...

Страница 39: ... 10M only module 1 2 Cut Jumper JP3 on the second PPS 10M 3 Cut and remove the red wires from the 15 cable in the PCK 1 kit P N 500 695066 when connecting between the two PPS 10Ms 4 Refer to Appendix E for cabling connections in a PSE 2 Enclosure Wiring to the PNC 2Z Refer to Table 11 Dress the field wiring that will be going to the PNC 2Z terminals Strip the insulation from the wiring and connect...

Страница 40: ...ules require labels PCM 1 PZE 4B zone label zone label terminal block label terminal block label Install the PXL Connection Diagram P N 575 294138 and the PXL Alarm Verification Label P N 575 294201 on the inside front cover of the enclosure STEP 16 Install the Door to the Backbox Replace the door on the hinges of the backbox STEP 17 Power up the PXL Turn on the AC power to the System The power li...

Страница 41: ...t See Figure 21 The user interface is password protected and menu driven It allows the user to enter all software selectable options The user interface has a 4 line by 20 character LCD display which maps functions to 8 keys The interface also includes a 12 button alphanumeric keypad for special programming functions The PCM 1 has the following 6 system status LEDs Power Trouble Alarm Audibles Sile...

Страница 42: ... SUPERVISORY LED and the appropriate zone LEDs The following screen is displayed on the PXL SUPV 1 OF 1 LOCATION ACKNOWLEDGE SUPV S Trouble A Trouble condition is displayed by a lighted TROUBLE LED along with the appropriate LEDs corresponding to the zone in trouble The following screen is displayed on the PXL TROUBLE 1 OF 1 LOCATION ACKNOWLEDGE TRBL S For a description of the system trouble messa...

Страница 43: ...e System ALARM LED and the appropriate Zone ALARM LED on the front panel to flash and the system s internal audible to sound NOTE Building occupants should follow the fire emergency evacu ation plan approved by the building owner Then alert the local Fire Department TO ACKNOWLEDGE ALARMS 1 Unlock and open the door 2 System operator should ACKNOWLEDGE the Fire Alarm by pressing the ACKNOWLEDGE butt...

Страница 44: ...nowledged and all conditions are returned to normal Responding to a Trouble Condition HOW THE SYSTEM ANNUNCIATES TROUBLES When a trouble is detected the system causes the TROUBLE LED and the appropriate Zone TROUBLE LEDs on the front panel to flash and the system s internal audible to sound TO ACKNOWLEDGE TROUBLES 1 Unlock and open the door 2 Press the ACKNOWLEDGE button to acknowledge the trouble...

Страница 45: ... user interface at any point in the program to access the Help screens These screens give a more detailed expla nation of the function to be performed The arrows on the screen indicate the button to press to select a particular item Firmware Revisions This manual references PXL firmware Revision 4 0 Make note of the following information for proper system operation PXL systems containing two PPS 1...

Страница 46: ...isplays the following question DO YOU WANT TO CONFIGURE THE SYSTEM NOW NO YES Answering YES by pressing the appropriate key on the user inter face starts the Automatic System Configuration mode This mode steps the user through every System programming option with a minimum of instruction Figure 22 shows how the Automatic System Configuration mode is mapped out Technical Manuals Online http www tec...

Страница 47: ...MENU is denied if unacknowledged alarms exist Figure 23 provides the entire menu tree including the Program Test Control and History options The user can use this tree at any time to determine the current location in the menu In order to make a change to the System configuration the user must first enter a passcode The System default is 123456 To change a passcode go to the Program section of the ...

Страница 48: ...PXL Conventional Fire Alarm Control Panel Programming 42 Figure 23 PXL Normal Operating Mode Technical Manuals Online http www tech man com firealarmresources com ...

Страница 49: ...of the System ASC leads the user through the different pro gramming functions The default values of all programmable features are displayed and the user has the opportunity to change each one If no selection is made during the ASC routine the screen will time out in 20 minutes and start its normal operating mode with all func tions operating in default program mode When a new module s is added to ...

Страница 50: ...s Thirty events can be stored in each category Events are stored sequentially Once 30 events are reached new events overwrite previous events HISTORY CLEAR This feature allows the installer to clear all history events from the system s memory One operation clears history for all event types This can be done after installation to clear those events associated with system start up testing and troubl...

Страница 51: ...characters assigned to them KEY ASSIGNED CHARACTERS KEY ASSIGNED CHARACTERS 1 2 3 4 5 6 A B C 1 D E F 2 G H I 3 J K L 4 M N O 5 P Q R 6 7 8 9 0 S T U 7 V W X 8 Y Z _ 9 0 Future Use Future Use When the custom message field is completed press the DONE button RESPONDING MODULES This Program selection allows the user to review the system modules installed in and reporting to the PXL SET ALARM VERIFICA...

Страница 52: ...e Retard Reset time and therefore would cause the Alarm Verification time to exceed 30 seconds r o t c e t e D p u t r a t S y a l e D s d n o c e S H 3 3 I D 5 H 3 A 3 A I D 5 H 3 B 3 B I D 5 1 9 1 1 A B P 1 T 3 3 E P 0 3 T 1 1 1 1 E P 0 5 SET BELL CODES This is a two step process First individual bell circuits are set as STEADY CODED or NON SILENCEABLE Then the code is selected one time for all ...

Страница 53: ...et any programmable relay to operate on either any alarm any supervisory condition or any trouble condition Global relays will not change state when a Generic zone is activated SET NAC CUTOFF TIMER This Program selection allows the user to select the length of time the signaling devices will activate before they are automatically silenced A selection of 0 disables the cutoff timer SET NAC INHIBIT ...

Страница 54: ... zone A detector supervised with Alarm Verification is turned off by the System immediately after it reaches an alarm threshold The detector is verified for a length of time which must not exceed 60 seconds After power is restored to the device and for the next 60 seconds if the detector once again reaches the alarm threshold the system will report an alarm condition If after 60 seconds the detect...

Страница 55: ...utput from an other control panel This output should be made with a contact device connected across the Generic zone When activated it causes the notification appliance circuits to sound and the appropri ate initiating Zone LED to light When the input is deactivated the NACs will silence regardless of any inhibit timer The System alarm contacts do not change state Do not map Generic zones to non s...

Страница 56: ...PXL Conventional Fire Alarm Control Panel Programming 50 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 57: ...STOM MESSAGES PROGRAMMABLE RELAYS 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ADDRESSING 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 5 5 5 5 5 5 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 4 5 5 5 5 5 5 NOTE All installed IDCS default to GENERAL ALARM NOTE All grayed tex...

Страница 58: ...52 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 59: ...owing two ways 1 When an initiating device is activated the system notification appliances sound steady and the appropriate zone LED turns on for 2 seconds or 2 When an initiating device is activated only the appropriate zone LED turns on for 2 seconds Notification appliances are not turned on Note Devices tested on supervisory zones will annunciate twice The first time is when the device is moved...

Страница 60: ...pplicable 2 If the PARTIAL SYSTEM DISABLE LED is lit check that all appropriate detectors are armed 3 Activate a detector or alarm initiating device To test for Go No Go operation use CERBERUS PYROTRONICSTM Test Gas P N 315 282747 following the instructions on the label Check that the detector LED lights and that the proper indication is given at the Control Panel 4 Verify that an alarm can be ack...

Страница 61: ...M 1 not connected or loose 2 Power data cable not connected or loose PNC 2Z 1 Power data cable from JP2 of the PPS 10M power supply to JP7 of the PCM 1 not connected or loose 2 Power data cable not connected or loose 3 EOL device s not connected PZE 4B 1 Power data cable not connected or loose 2 EOL device s not connected or loose LED 3 4 1 Power data cable not connected or loose 2 Polling LED not...

Страница 62: ... changed LED 3 4 MOD X NOT SPEC D LED 3 4 responding but not in configuration LED module added but system not reconfigured LED module address changed MULTI RESP LED 3 4 MOD X Multiple Response at LED 3 4 address Two LED modules set to same address LED set to address out of range MULTI RESP PCM MOD O Multiple Response at PCM address Module failed MULTI RESP PNC MOD X Multiple Response at PNC addres...

Страница 63: ... D PPS responding but not in configuration PPS module added but system not reconfigured PPS module address changed PPS MOD X WATCHDOG PPS module watchdog Module locked up reset the panel PPS1 AUX PWR FAULT Auxiliary power trouble on first PPS 10M in PXL System Aux power fuse blown PPS1 BATTERY FAULT Battery trouble on first PPS 10M in PXL System Battery missing not connected Battery high Battery l...

Страница 64: ...ng reset PCM 1 and or PZE 4B module has Rev 1 0 firmware Upgrade to Rev 3 x or higher RELAY XX BYPASSED Relay bypassed Relay bypassed RSA MOD X MULTI UNKN RSA not responding and ASC routine will not run Two or more RSAs installed with same dipswitch address RSA MOD X NO RESPONSE RSA not responding Module removed from system Module failed Module address changed RSA MOD X NOT SPEC D RSA responding b...

Страница 65: ...ces notification appliance circuits programmable relays and system mapping for the PXL Complete the worksheets before you start to enter data into the program configuration When you have completed programming the PXL transfer to final configuration data to Table 13 for permanent reference Technical Manuals Online http www tech man com firealarmresources com ...

Страница 66: ... O N N N N N N N N N N N N E E E E E E E E E E E E 1 2 3 4 5 6 7 8 9 10 11 12 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 33 30 34 31 35 32 36 14 13 12 11 10 9 8 7 6 5 4 3 2 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 4 5 5 5 5 5 5 NOTE All installed IDCS default to GENERAL ALARM NOTE All grayed text indicates default programming MODULE ADDRESSING PCM PZE No 1 PZE No 2 PZE No 3 PZE No 4 PZE N...

Страница 67: ...MPORAL MARCH TIME ADDRESSING NON SILENCEABLE 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 B B B B E E E E L L L L L L L L 1 2 3 4 X X X X 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 3 3 3 4 4 4 4 4 4 5 5 5 5 5 5 NOTE All installed NACS default to STEADY MODULE PPS No 1 PPS No 2 PNC No 1 PNC No 2 PNC No 3 PNC No 4 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 68: ...9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 ADDRESSING 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 4 4 4 4 4 4 4 4 5 5 5 5 5 5 5 5 MODULE PRM No 1 PRM No 2 PRM No 3 PRM No 4 PRM No 5 PRM No 6 PRM No 7 PRM No 8 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 69: ...Appendix A PXL Conventional Fire Alarm Control Panel 63 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 70: ...PXL Conventional Fire Alarm Control Panel Appendix A 64 Technical Manuals Online http www tech man com firealarmresources com ...

Страница 71: ...____A PNC 2Z Module s Number of modules ________ x 0 036A ______A PRM 4 Module s Number of modules ________ x 0 060A ______A LED 3 4 Module s Number of modules ________ x 0 042A ______A RSA Module s RSA 16R RSA 16B 220ma RSA 16RTL RSA 16BTL 450mA RSA 16RSC RSA 16BSC 450mA Number of modules ________ x ________A ______A 4 IDC Zones in Alarm 0 720A 0 720A Total Current Must be 1 8A or less per PPS 10...

Страница 72: ...__ NAC 13 ________ NAC 14 ________ NAC 15 ________ NAC 16 ________ 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A 0A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A ______A LED 3 4 Module s Number of modules ________ x 0 009A Standby ________ x 0 042A Alarm ______A ______A RSA Module s Number of modules ________ x 0 0...

Страница 73: ...ware revisions for the following PNC 2Z modules PRM 4 modules RSA series annunciators Programming the PXL Whether programming the System from the Automatic System Configuration routine or in the Program Mode accessible from the Main Menu the Country Code must be set for Canada This will cause the first alarm supervisory or trouble condition to be continu ously reported on the Liquid Crystal Displa...

Страница 74: ...nnect the battery to the PPS 10M through the supervisory relay Connect the NO contact to Battery terminal and Common to Bat terminal of the PPS 10M Connect Battery terminal to Bat of the PPS 10M If a supervisory relay is required use a PRM 4 and configure the relay as a global supervisory Figure 25 PPS 10M Wiring for Canadian Automatic Battery Disconnect Technical Manuals Online http www tech man ...

Страница 75: ...e used to annunciate conditions other than fire INSTALLATION Remove all system power before installation first battery and then AC To power up connect the AC first and then the battery Mounting Silent Knight Model 5128 Mount the Silent Knight Model 5128 within the PXL enclosure as shown in Figure 26 When mounting the unit in either the PSE 1 or PSE 2 enclosure place the Silent Knight Model 5128 be...

Страница 76: ...he Alarm Trouble and Supervisory dry contacts on the PXL Main Board In NFPA 72 Central Station connections AC fail reporting is delayed The delay is typically 6 hours Only the reporting of the trouble is delayed In NFPA 72 Remote Station connections provide 60 hour back up battery capacity ELECTRICAL CHARACTERISTICS Supervisory 84mA 18 40 VDC Alarm 154mA 18 40 VDC Technical Manuals Online http www...

Страница 77: ... 140 820388 are not provided These 4 7K 1 2W 5 EOLRs are needed for full installation 2 For Remote Station provide 60 hour back up battery capacity Figure 27 PXL to Silent Knight Model 5128 5129 Wiring Diagram Technical Manuals Online http www tech man com firealarmresources com ...

Страница 78: ...ote Sation b If the Silent Knight Model 5128 Digital Fire Communicator is used enter 0 hours 5 The PXL must be programmed to delay the trouble relay on AC fail Follow the steps below a Enter the Program mode b From the Set Timers menu select Set AC Fail Relay Delay to 6 hours for Central Station applications or 15 hours for Remote Station applications No Option Name Select 1 ZONE ACTIVE 0 2 ZONE S...

Страница 79: ... PRM 4 JP2 JP2 JP2 JP1 JP1 JP1 JP1 JP2 JP2 JP2 JP1 PZE 4B PZE 4B JP7 Components are underneath the board 1 1 1 1 11 JP7 JP6 JP6 PZE 4B JP1 JP1 1 1 1 1 1 1 1 1 1 1 1 1 1 PNC 2Z or PRM 4 PNC 2Z or PRM 4 PNC 2Z or PRM 4 PNC 2Z or PRM 4 PNC 2Z or PRM 4 PNC 2Z or PRM 4 PNC 2Z or PRM 4 PNC 2Z or PRM 4 15 CABLE FROM PCK 1 KIT P N 500 695066 WITH RED CONDUCTORS CUT AND REMOVED MOUNTED ON FIRST PMK 1 BRACK...

Страница 80: ... PZE 4B PZE 4B JP7 Components are underneath the board 1 1 1 1 11 JP7 JP6 JP6 PZE 4B JP1 JP1 1 1 1 1 1 1 1 1 1 1 1 MOUNTED ON FIRST PMK 1 BRACKET MOUNTED ON SECOND PMK 1 BRACKET 15 CABLE FROM PCK 1 KIT P N 500 695066 WITH ALL CONDUCTORS PZE 4B PZE 4B JP7 JP6 JP7 JP6 JP7 JP6 JP7 JP6 PCM 1 1 1 1 1 1 1 PTX 12 TRANSFORMER JP2 JP2 JP1 1 PRM 4 PRM 4 JP1 JP1 JP2 JP2 1 1 1 1 BP 61 15AH BATTERY _ Technical...

Страница 81: ...d battery enclosure 7 In all cases the Siemens Building Technologies Inc model number is the compatibility identi fier including the control panel module s and all compatible initiating devices 8 All power limited wiring requires separation from non power limited wiring Refer to the PSE 1 Installation and Power Limited Wiring Instructions P N 315 094154 9 Combination of NAC power and AUX power can...

Страница 82: ... Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of this equipment in a residential area is likely to cause interference in which case the user at his own expense will be required to take whatever measures may be required to correct the interference Technical ...

Страница 83: ...s Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 CN Technical Manuals Online http www tech man com firealarmresources com ...