10.8.7 Switch off
10.8.7.1 Safety during switch-off
WARNING
System parts that have been switched off make it impossible to acquire and
process alarms or faults!
Fire may spread unhindered.
● Deploy staff to monitor the deactivated area.
● You must switch deactivated parts of the 'Site' back on as soon as possible.
10.8.7.2 Switching off the detector line
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > ↑ 'Station' > ↑ Line card >
↑ Detector line.
2. Press the 'MoreOptions' softkey and select 'Execute commands'.
3.
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select the 'Detector line OFF' command.
The yellow 'ISOLATION' LED lights up.
The detector line is switched off.
10.8.7.3 Switch off zone
1. Select 'Topology' > ↑ 'Detection tree' > 'Area' > ↑ 'Section' > 'Zone' in the main
menu.
2. Press the 'More Options' softkey and select 'Execute commands'.
3.
WARNING! System parts that have been switched off make it impossible to
acquire and process alarms or faults! Select the 'Off' command.
The yellow 'ISOLATION' LED lights up.
The 'Zone' is switched off.
10.8.8 Switching on
10.8.8.1 Switch on detector line
1. Select 'Main menu' > 'Topology' > 'Hardware tree' > 'Station' > ↑ Line card >
↑ Detector line.
2. Press the 'MoreOptions' softkey and select 'Execute commands'.
3. Select the 'Detector line ON' command.
The yellow 'ISOLATION' LED goes out.
The detector line is switched on.