Commissioning
Displaying C-NET devices
10
90 | 118
Building Technologies
A6V10211100_f_en_--
Fire Safety
2015-12-15
4. Select the corresponding 'C-NET line card (onboard/FCL2001)' Module and
press the 'Lower level' <softkey>.
All lines of 'C-NET line card (onboard/FCL2001)' are indicated.
5. Select a line and press 'More Options'' <softkey>.
The 'Select option' window is open.
6. Select 'Execute commands' and confirm with <ok>.
The window including the possible commands is displayed.
7. Select the 'Show details' command and confirm with <ok>.
The details are displayed.
Example of selecting a line
004 Elements
C-NET line card
(onboard/FCL2001)
Module 2
Line
Line
Line
Line
11
12
21
22
Line
Line
Line
Line
Upper
level
Lower
level
More
Options
004 Elements
Line 12
Device
Device
Device
Device
11
12
21
22
OH720
HI720
OP720
OP720
Upper
level
Lower
level
More
Options
κ
Check whether all devices of this C-NET detector line are displayed correctly.
You can use the type designation to detect the type of device displayed (smoke
detector, heat detector, manual call point etc.)
You will find a list of type designations in the 'C-NET devices' chapter