![Siemens Add 7 AddFEM Скачать руководство пользователя страница 77](http://html.mh-extra.com/html/siemens/add-7-addfem/add-7-addfem_manual_377066077.webp)
Technical Data
AddFEM
4-26
AddFEM
C79000–G8076–C900–03
Analog value representation for symmetrical (bipolar) measuring ranges:
System
Measuring range
Value
Dec.
Hex.
"
20 mA
"
30 mA
"
50 mA
"
10 V
Re-
mark
118.507%
32764
7FF
C
23.70 mA
35.549 mA
59.25 mA
11.85 V
Over-
flow
117.596%
32512
7F00
117.582%
32508
7EF
C
23.52 mA
35.271mA
58.80 mA
11.76 V
Over-
range
27652
6C04
100%
27648
6C00
20 mA
30 mA
50 mA
10 V
0.014468%
4
4
0.002893 mA
0.00434 mA
0.00723 mA
0.014468 V
Nomi-
0 %
0
0
0 mA
0 mA
0 mA
0 V
Nomi-
nal
–0.014468%
–4
–4
–0.002893m
A
–0.00434mA
–0.00723mA
–0.014468V
range
–100%
–2764
8
9400
–20 mA
–30 mA
–50 mA
–10 V
–2765
2
93FC
Under-
range
–17.596%
–3251
2
8100
–23.52 mA
–35.276 mA
–58.80 mA
–11.76 V
–3251
6
80FC
Under-
flow
–118.521%
–3276
8
8000
–23.70 mA
–35.55 mA
–59.25 mA
–11.85 V
Value
2
1
5
2
1
4
2
1
3
2
12
2
11
2
10
2
9
2
8
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Bit No.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
As-
sign.
PS
x
x
x
x
x
x
x
x
x
x
x
x
x
x
QU
Meaning:
PS = Preceding sign :
0
³
Positive
1
³
Negative
x = Analog value as fixed–point number (13 bits)
QU = Qualifier :
0
³
Analog value OK
1
³
Analog value faulty
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Add 7 AddFEM
Страница 7: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 27: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 51: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 81: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...