![Siemens Add 7 AddFEM Скачать руководство пользователя страница 58](http://html.mh-extra.com/html/siemens/add-7-addfem/add-7-addfem_manual_377066058.webp)
AddFEM
Technical Data
4-7
AddFEM
C79000–G8076–C900–03
Period T since the last pulse
Limiting of the frequency output to following
values
0..to max. 2 msec
Old frequency is retained. Since the cycle time
for the detection amounts to 2 msec, a mis-
sing pulse can no longer be detected.
2 to max. 4 msec
Limitation to max. 750 Hz
4 to max. 6 msec
Limitation to max. 375 Hz
8 to max. 10 msec
Limitation to max. 187.5 Hz
18 to max. 20 msec
Limitation to max. 83.3 Hz
48 to max. 50 msec
Limitation to max. 31.3 Hz
98 to max. 100 msec
Limitation to max. 15.3 Hz
0.998 to max. 1 sec
Limitation to max. 1.5 Hz
9.998 to max. 10 sec
Limitation to max. 0.15 Hz
> 10 sec
Output is set to 0 (i.e. frequencies under 0.1
Hz are not detected or always set to 0)
Further information on the counting pulse inputs at wire breaks at
6DL3100–8AA/–8AB with versions below 7 can be found in the product information
which is contained on the same document CD.
B) Behavior of the two–channel counting pulse/speed detection
(with sense of rotation recognition) if one of the channels fails:
(applies for 6DL3100–8AA as from Version 8, 6DL3100–8AB as from Version 7,
all 6DL3100–8AC)
If one of the two channels fails, the value of the speed of the failed channel is redu-
ced step–by–step to 0, as in single–channel detection. The sign is frozen with the
state which it had before the fault occurred. This ensures that speed recognition is
still possible on one channel. However, changes in the direction of rotation are no
longer recognized.
Note
For a configuration suggestion on monitoring for wire breaks please refer to Section
3.1.3 ”Operating principle of the 2–channel speed detection with recognition of the
sense of rotation”
Caution
Operation of the counting pulse/speed detection with sense of rotation recognition (for
use at water turbines) with versions below those specified above is not permitted,
since the speed and sense of rotation are sporadically no longer recognized correctly
when a sensor fails or a wire breaks (jumps in the values).
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Add 7 AddFEM
Страница 7: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 27: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 51: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 81: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...