![Siemens Add 7 AddFEM Скачать руководство пользователя страница 59](http://html.mh-extra.com/html/siemens/add-7-addfem/add-7-addfem_manual_377066059.webp)
Technical Data
AddFEM
4-8
AddFEM
C79000–G8076–C900–03
Digital Outputs
1)
Number of outputs
16 digital semiconductor outputs
Nominal output voltage
24 V DC
Output voltage at 0 signal
<
1 V
Output voltage at 1 signal
Supply voltage –2 V
Max. output current
500 mA
Parallel connection of outputs for higher cur-
rents is possible.
Output current at 100% coincidence factor
500 mA
Total output current
8 A
Effects of multiple overloads on multiple circuit
modules
None
Short–circuit to ground monitoring
Yes
Short–circuit strength
Yes
Max. lamp load per output
5 W
Inductive loads
Typical values:
Maximum inductivity at I
v
500 mA
Connection of inductive loads is possible. Inte-
grated suppressor diodes with a higher extinc-
tion voltage of 39 V than the normal free–
wheeling diode lead to rapid disconnection of
the current and thus of the actuating element.
However, the maximum extinction current (1
W) may not be exceeded.
8 H (without external suppressor diode)
Maximum inductivity at I
v
500 mA
and f
v
1 Hz
Maximum inductivity at I
t
250 mA
and any f
Maximum inductivity at external suppressor
diode
8 H (without external suppressor diode)
Unlimited
Unlimited
Output delay time (TQD, dead time) from com-
mand output to response of the output (begin-
ning of the current rise)
20
µ
s for signal transitions from 0 to 1
20
µ
s for signal transitions from 1 to 0
Output response time (TQT) from command
output until the full output current is reached at
500 mA
50
µ
s for signal transitions from 0 to 1
50
µ
s for signal transitions from 1 to 0
Behavior of the outputs at interruption of the
operation controlled by the main processing
unit
The outputs are de–activated
Behavior of the outputs at collapsing and inter-
ruptions of the supply voltage L1+ resp. L2+ at
X7/1 resp. X7/11
The output voltage of the outputs follows the
supply voltage.
Display
The voltage level of the digital outputs are de-
tected via additional module–internal digital
inputs, converted and read by the internal mi-
cro controller unit. The micro controller unit
displays these read–back states at the LED
on the front.
Configuration of the terminals
Refer to Appendix A, connector X7, Page A-2
1)
Digital outputs can also be used as digital inputs!
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Add 7 AddFEM
Страница 7: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 27: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 51: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 81: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...