![Siemens Add 7 AddFEM Скачать руководство пользователя страница 105](http://html.mh-extra.com/html/siemens/add-7-addfem/add-7-addfem_manual_377066105.webp)
Commissioning / Operation / Maintenance
AddFEM
5-24
AddFEM
C79000–G8076–C900–03
Error Displays
LED
Error
type
Display
Cause
INTF
Internal
error
Errors determined by self monitoring:
•
RAM memory test
•
Check sum of correction factors
•
Check sum of program code flash EPROM or RAM
EXTF
External
error
•
Process signal “Analog Out” faulty
•
Process signal “Analog In” faulty
•
Process signal “Digital Out” faulty
•
The 24 V DC load supply for the digital outputs is missing
BUSF1
Bus error 1
Errors determined by self monitoring at the PROFIBUS DP
connection X3A:
•
Master monitoring has triggered
•
Sign of life has failed
Parameterization error via PROFIBUS DP connection X3A:
•
The received configuration message contains invalid parameter
values.
•
At 2–channel configuration: The received parameter values
deviate from the configuration via the PROFIBUS DP connec-
tion X3B.
BUSF2
Bus error 2
Errors determined by self monitoring at the PROFIBUS DP
connection X3B
•
Master monitoring has triggered
•
Sign of life has failed
Parameterization error via PROFIBUS DP connection X3B:
•
The received configuration message contains invalid parameter
values.
•
At 2–channel configuration: The received parameter values
deviate from the configuration via the PROFIBUS DP connec-
tion X3A.
RED
Redun-
dancy error
At module redundancy: The optical–fiber cable coupling between the
redundant AddFEMs has failed.
Compatibility test at the module redundancy in the LINK–UP state:
•
The redundant AddFEMs were configured differently
•
The master and the reserve modules have different firmware
version states
Lighting
Flashing
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Содержание Add 7 AddFEM
Страница 7: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 27: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 51: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...
Страница 81: ...Artisan Technology Group Quality Instrumentation Guaranteed 888 88 SOURCE www artisantg com ...