Manual 7XV5655-0BB00
SIEMENS AG
Page 7 of 79
C53000-G1176-C175-3
Scope of Supply
•
Serial Modem, device for DIN rail mounting
•
Gender changer, 9-way, male-male
•
CD with manual, configuration tool, and Serial Modem driver
•
Installation
instructions
Unpacking and Repacking
The devices are factory-packed to meet the requirements of IEC 60255–21.
Unpacking and re-packing must be performed with the usual care, without force and
only with the aid of suitable tools. Visually check the device immediately upon arrival for
correct mechanical condition.
Please also always follow instructions if they are supplied with the device.
The shipping packaging can be re-used in the same manner for further shipment.
Note that the storage packaging of individual devices is not sufficient for shipping.
If other packaging is used, the shock requirements acc. to IEC 60255–21–1 Class II and
IEC 60255–21–2 Class 1 must be met.
The device should be stored in the final operating area for a minimum of two hours
before the power source is first applied. This gives the device time to acclimatise to the
temperature equilibrium, thus avoiding dampness and condensation.
Storage
SIPROTEC
®
devices and associated parts should be stored in a dry and clean place.
The device as well as its replacement modules must be stored within the temperature
range, which is –10 °C to +55 °C.
The relative humidity is not allowed to lead to condensation or ice.
To avoid premature ageing of the electrolyte capacitors in the power supply unit, a
temperature range of +10 °C to +35 °C (+50 °F to +95 °F) is recommended for storage.
After extended storage, the power supply of the device should be energised,
approximately every two years, for one or two days to regenerate the electrolytic
capacitors in the power supply unit. This should also be done before the device is put
into service.