Manual 7XV5655-0BB00
C53000-G1176-C175-3
Page 10 of 79
SIEMENS AG
Features
Protocol detection for VDEW / IEC60870-5-101/103 and DIGSI® protocol (similar
to IEC60870-5-103), UDP protocol without error detection and correction
RS232/RS485 (switchable port) or FO interface for data transfer and modem
configuration.
Serial baudrate and data format to the terminals can be set from 2400 Bd to
115.2 kBd with data formats 8N1, 8N2, 8E1.
Reset to default values (factory settings) with INIT button: 9600 baud, 8N1
A 10-Mbit Ethernet interface (10BaseT) for the 10/100 Mbit network.
DIP switch for RS232/RS485 selection and RS485 bus termination as well as
FO idle state
Enhanced security possible by password protection and IP address selection.
LED displays for operating voltage and data traffic are located on the front panel
DIN rail module in the plastic housing with integrated wide-range power supply
unit (24 - 250 V DC and 60 - 230 V AC) which provides connection to all
conventional substation batteries or AC power systems.
Protective conductor (PE) connection
Easy configuration with the configuration tool
Configuration tool V15 for
Microsoft Windows
®
XP Prof. 32-Bit SP3
Microsoft
Windows
®
7 Prof. 32-Bit SP1
Microsoft
Windows
®
7 Prof. 64-Bit SP1
Microsoft
Windows
®
Server 2008 R2 / 64-Bit