English
7XV5461-0Bx00
68
C53000-B1174-C173-5
Vibration and Shock Stress During Transport
Standards:
IEC 60255-21 and IEC 60068-2
– Vibration
Sinusoidal
IEC 60255-21-1, Class 2
5 Hz to 8 Hz:
±
7.5 mm Amplitude
IEC 60068-2-6
8 Hz to 150 Hz: 2 g acceleration
Frequency sweep rate 1 Octave/min
20 cycles in 3 orthogonal axes.
– Shock
Half-sine shaped
IEC 60255-21-2, Class1
Acceleration 15 g, duration 11 ms,
IEC 60068-2-27
3 shocks in each direction of
3 orthogonal axes.
– Continuous Shock
Half-sine shaped
IEC 60255-21-2, Class 1
Acceleration 10 g, duration 16 ms,
IEC 60068-2-29
1000 shocks in each direction of
3 orthogonal axes.
Climatic Stress Tests
Temperatures
IEC
60068–2
– Recommended temperature during operation
-5 °C to +55 °C or +23 °F to +131 °F
– Permissible temporary (transient)
operating temperature
-20 °C to +70 °C or -4 °F to +158 °F
– Type test (acc. IEC 60068–2–1 and –2
-25 °C to +85 °C or -13 °F to +185 °F
Test Bd for 16 h)
– Limit temperatures during storage
-40 °C to +85 °C or -40 °F to +185 °F
– Limit temperatures for operation
-40 °C to +85 °C or -40 °F to +185 °F
Storage and transport of the device with factory packaging!