Chapter 6) 7SR158 Commissioning & Maintenance Guide
Chapter 6 - Page 6 of 24
©2013 Siemens Protection Devices Limited
1.2.3
Test Equipment
Required test equipment is:
1. Secondary injection equipment with integral time interval meter
2. Primary injection equipment
3. A power source with nominal voltage within the working range of the relay's auxiliary supply rating.
4. A power source with nominal voltage within the working range of the relay’s binary input rating.
5. Other equipment as appropriate to the protection being commissioned – this will be specified in the
product specific documentation.
The secondary injection equipment should be appropriate to the protection functions to be tested. Additional
equipment for general tests and for testing the communications channel is:
6. Portable PC with appropriate interface equipment.
7. Printer to operate from the above PC (Optional).
1.2.4
Use of PC to facilitate testing
The functions of Reydisp Evolution (see Section 2: Settings and Instruments) can be used during the
commissioning tests to assist with test procedures or to provide documentation recording the test and test
parameters. One method is to clear both the waveform and event records before each test is started, then, after
the test upload from the relay the settings, events and waveform files generated as a result of application of the
test. These can then be saved off to retain a comprehensive record of that test.
Relay settings files can be prepared on the PC (offline) or on the relay before testing commences. These settings
should be saved for reference and compared with the settings at the end of testing to check that errors have not
been introduced during testing and that any temporary changes to settings to suit the test process are returned to
the required service state.
A copy of the Relay Settings as a Rich Text Format (.rtf) file suitable for printing or for record purposes can be
produced from Reydisp as follows. From the
File
menu select
Save As,
change the file type to
Export
Default/Actual Setting (.RTF)
and input a suitable filename.
When testing is completed the event and waveform records should be cleared and the settings file checked to
ensure that the required in-service settings are being applied.
1.2.5
Precautions
Before electrical testing commences the equipment should be isolated from the voltage transformers. The tripping
and alarm circuits should also be isolated where practical. The provision and use of secondary injection test
sockets on the panel simplifies the isolation and test procedure.
Ensure that the correct auxiliary supply voltage and polarity is applied. See the relevant scheme diagrams for the
relay connections.
1.2.6
Applying Settings
The relay settings for the particular application should be applied before any secondary testing occurs. If they are
not available then the relay has default settings that can be used for pre-commissioning tests. See the Relay
Settings section of this manual for the default settings.
Note that the tripping and alarm contacts for any function must be programmed correctly before any scheme tests
are carried out.
Relays feature multiple settings groups, only one of which is active at a time. In applications where more than one
settings group is to be used it may be necessary to test the relay in more than one configuration.
Note.
One group may be used as a ‘Test’ group to hold test-only settings that can be used for regular
maintenance testing, eliminating the need for the Test Engineer to interfere with the actual in-service settings in
the normally active group. This Test group may also be used for functional testing where it is necessary to disable
or change settings to facilitate testing.
Содержание 7SR158 Argus
Страница 1: ...Answers for energy 7SR158 Argus Voltage and Frequency Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR158 Argus Contents ...
Страница 10: ...Chapter 1 7SR158 Description of Operation Chapter 1 Page 6 of 38 2014 Siemens Protection Devices Limited ...
Страница 44: ...Chapter 2 7SR158 Technical Manual Chapter 2 Page 2 of 16 2013 Siemens Protection Devices Limited ...
Страница 46: ...Chapter 2 7SR158 Technical Manual Chapter 2 Page 4 of 16 2013 Siemens Protection Devices Limited ...
Страница 60: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 2 of 24 2013 Siemens Protection Devices Limited ...
Страница 62: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 4 of 24 2013 Siemens Protection Devices Limited ...
Страница 82: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 24 of 24 2013 Siemens Protection Devices Limited ...
Страница 84: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 2 of 66 2013 Siemens Protection Devices Limited ...
Страница 88: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 6 of 66 2013 Siemens Protection Devices Limited ...
Страница 102: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 20 of 66 2013 Siemens Protection Devices Limited ...
Страница 114: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 32 of 66 2013 Siemens Protection Devices Limited ...
Страница 138: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 56 of 66 2013 Siemens Protection Devices Limited ...
Страница 140: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 58 of 66 2013 Siemens Protection Devices Limited ...
Страница 150: ...Chapter 5 7SR158 Installation Guide Chapter 5 Page 2 of 14 2013 Siemens Protection Devices Limited ...
Страница 152: ...Chapter 5 7SR158 Installation Guide Chapter 5 Page 4 of 14 2013 Siemens Protection Devices Limited ...
Страница 164: ...Chapter 6 7SR158 Commissioning Maintenance Guide Chapter 6 Page 2 of 24 2013 Siemens Protection Devices Limited ...
Страница 188: ...Chapter 7 7SR158 Applications Guide Chapter 7 Page 2 of 24 2014 Siemens Protection Devices Limited ...
Страница 211: ......