2.8 Binary Outputs (Output Relays)
All outputs are fully user configurable and can be programmed to operate from any or all of the available
functions.
In the default mode of operation binary outputs are self reset and remain energised for a user configurable
minimum time of up to 60 seconds. If required, outputs can be programmed to operate as ‘hand reset’ or ‘pulsed’.
If the output is programmed to be ‘hand reset’ and ‘pulsed’ then the output will be ‘hand reset’ only.
Operating a binary output as ‘hand reset’ fulfils the requirements of ANSI function 86 (Lockout).
The binary outputs can be used to operate the trip coils of the circuit breaker directly where the trip coil current
does not exceed the 'make and carry' contact rating. The circuit breaker auxiliary contacts or other in-series
auxiliary device must be used to break the trip coil current.
Any BO can be assigned as a ‘Trip Contact’ in the OUTPUT CONFIG>TRIP CONFIG menu. Operation of a ‘Trip
Contact’ will operate any LED or virtual assigned from the ‘Trip Triggered’ feature in the same menu and will
initiate the fault record storage, actuate the ‘Trip Alert’ screen where enabled and CB Fail protection when
enabled.
Where a protection function is mapped to an output contact, the output contact can be configured to trigger when
the protection function picks-up rather than when it operates. Such output contacts are configured via the
OUTPUT CONFIG>BINARY OUTPUT CONFIG>
Pickup Outputs
setting.
Contacts in the case ensure that the normally closed binary outputs remain short circuited when the relay is
withdrawn from the case.
Notes on Self Reset Outputs
Outputs reset after the initiate condition is removed, they are subject to the user definable ‘Minimum Operate
Time’ setting.
With a failed breaker condition the relay may remain operated until current flow in the primary system is
interrupted by an upstream device. The relay will then reset and attempt to interrupt trip coil current flowing
through an output contact. Where this level is above the break rating of the output contact an auxiliary relay with
heavy-duty contacts should be utilised.
Notes on Pulsed Outputs
When operated, the output will reset after the user definable ‘Minimum Operate Time’ setting regardless of the
initiating condition.
Notes on Hand Reset Outputs – 86 Lockout
Any binary output can be programmed to provide an 86 lockout function by selecting it to be hand reset. Hand
reset outputs can be reset by either pressing the
TEST/RESET
button, by energising a suitably programmed
binary input, or, by sending an appropriate command over the data communications channel(s).
On loss of the auxiliary supply hand-reset outputs will reset. When the auxiliary supply is re-established the binary
output will remain in the reset state unless the initiating condition is still present.
Binary Output Test
The MAINTENANCE>OUTPUT MATRIX TEST menu includes a facility to test output relays from the relay fascia
without the need for a secondary injection test set.
Binary outputs can also be energised from the Reydisp Evolution software package where PC facilities are
available.
Содержание 7SR158 Argus
Страница 1: ...Answers for energy 7SR158 Argus Voltage and Frequency Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR158 Argus Contents ...
Страница 10: ...Chapter 1 7SR158 Description of Operation Chapter 1 Page 6 of 38 2014 Siemens Protection Devices Limited ...
Страница 44: ...Chapter 2 7SR158 Technical Manual Chapter 2 Page 2 of 16 2013 Siemens Protection Devices Limited ...
Страница 46: ...Chapter 2 7SR158 Technical Manual Chapter 2 Page 4 of 16 2013 Siemens Protection Devices Limited ...
Страница 60: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 2 of 24 2013 Siemens Protection Devices Limited ...
Страница 62: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 4 of 24 2013 Siemens Protection Devices Limited ...
Страница 82: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 24 of 24 2013 Siemens Protection Devices Limited ...
Страница 84: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 2 of 66 2013 Siemens Protection Devices Limited ...
Страница 88: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 6 of 66 2013 Siemens Protection Devices Limited ...
Страница 102: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 20 of 66 2013 Siemens Protection Devices Limited ...
Страница 114: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 32 of 66 2013 Siemens Protection Devices Limited ...
Страница 138: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 56 of 66 2013 Siemens Protection Devices Limited ...
Страница 140: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 58 of 66 2013 Siemens Protection Devices Limited ...
Страница 150: ...Chapter 5 7SR158 Installation Guide Chapter 5 Page 2 of 14 2013 Siemens Protection Devices Limited ...
Страница 152: ...Chapter 5 7SR158 Installation Guide Chapter 5 Page 4 of 14 2013 Siemens Protection Devices Limited ...
Страница 164: ...Chapter 6 7SR158 Commissioning Maintenance Guide Chapter 6 Page 2 of 24 2013 Siemens Protection Devices Limited ...
Страница 188: ...Chapter 7 7SR158 Applications Guide Chapter 7 Page 2 of 24 2014 Siemens Protection Devices Limited ...
Страница 211: ......