Chapter 1) 7SR158 Description of Operation
©2014 Siemens Protection Devices Limited Chapter 1) Page 37 of 38
6.6 Control Mode
This mode provides convenient access to commonly used relay control and test functions. When any of the items
listed in the control menu are selected control is initiated by pressing the ENTER key. The user is prompted to
confirm the action, again by pressing the ENTER key, before the command is executed.
Note that a CB must be in a Closed state before an Open command will be accepted. And that a CB must be in
an Open state before a Close command will be accepted. If not, the Relay reports that the requested command is
‘Interlocked’.
Note also that switching a protection function IN / OUT via the Control Menu will not change that function’s
ENABLED / DISABLED setting. The Control Menu selection will over-ride the setting, however.
Control Mode commands are password protected using the Control Password function – see Section 6.9.
6.7 Real Time Clock
Time and date can be set either via the relay fascia using appropriate commands in the System Config menu or
via the data comms channel(s). Time and date are maintained while the relay is de-energised by a back up
storage capacitor. The length of time for which this data will be maintained will depend on such things as
temperature, length of time in service, etc. However the data will be maintained for a minimum of 1.8 days.
In order to maintain synchronism within a substation, the relay can be synchronised to the nearest second or
minute using the communications interface, or a binary input.
The default date is set at 01/01/2000 deliberately to indicate the date has not yet been set. When editing the
Time
, only the hours and minutes can be edited. When the user presses
ENTER
after editing the seconds are
zeroed and the clock begins running.
6.7.1
Time Synchronisation – Data Communication Interface
Where the data comms channel(s) is connected the relay can be directly time synchronised using the global time
synchronisation. This can be from a dedicated substation automation system or from ‘Reydisp Evolution’
communications support software.
6.7.2
Time Synchronisation – Binary Input
A binary input can be mapped
Clock Sync from BI
. The seconds or minutes will be rounded up or
down to the nearest vale when the BI is energised. This input is leading edge triggered.
6.8 Settings Groups
The relay provides four groups of settings – Group number (Gn) 1 to 4. At any one time only one
group of settings can be ‘active’ – SYSTEM CONFIG>
Active Group
setting. An output is provided to
indicate which setting group is active.
It is possible to edit one group while the relay operates in accordance with settings from another ‘active’ group
using the
View/Edit Group
setting.
Some settings are independent of the active group setting i.e. they apply to all settings groups. This is indicated
on the top line of the relay LCD – where only the
Active Group No
. is identified. Where settings are group
dependent this is indicated on the top line of the LCD by both the
Active Group No
. and the
View Group No
.
being displayed.
A change of settings group can be achieved either locally at the relay fascia, remotely over the data comms
channel(s) or via a binary input. When using a binary input an alternative settings group is selected only whilst the
input is energised (
Select Grp Mode: Level triggered
) or latches into the selected group after energisation of the
input (
Select Grp Mode: Edge triggered
).
Settings are stored in non-volatile memory.
Содержание 7SR158 Argus
Страница 1: ...Answers for energy 7SR158 Argus Voltage and Frequency Relay Reyrolle Protection Devices ...
Страница 2: ......
Страница 4: ...7SR158 Argus Contents ...
Страница 10: ...Chapter 1 7SR158 Description of Operation Chapter 1 Page 6 of 38 2014 Siemens Protection Devices Limited ...
Страница 44: ...Chapter 2 7SR158 Technical Manual Chapter 2 Page 2 of 16 2013 Siemens Protection Devices Limited ...
Страница 46: ...Chapter 2 7SR158 Technical Manual Chapter 2 Page 4 of 16 2013 Siemens Protection Devices Limited ...
Страница 60: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 2 of 24 2013 Siemens Protection Devices Limited ...
Страница 62: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 4 of 24 2013 Siemens Protection Devices Limited ...
Страница 82: ...Chapter 3 7SR158 Performance Specification Chapter 3 Page 24 of 24 2013 Siemens Protection Devices Limited ...
Страница 84: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 2 of 66 2013 Siemens Protection Devices Limited ...
Страница 88: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 6 of 66 2013 Siemens Protection Devices Limited ...
Страница 102: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 20 of 66 2013 Siemens Protection Devices Limited ...
Страница 114: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 32 of 66 2013 Siemens Protection Devices Limited ...
Страница 138: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 56 of 66 2013 Siemens Protection Devices Limited ...
Страница 140: ...Chapter 4 7SR158 Data Communications Chapter 4 Page 58 of 66 2013 Siemens Protection Devices Limited ...
Страница 150: ...Chapter 5 7SR158 Installation Guide Chapter 5 Page 2 of 14 2013 Siemens Protection Devices Limited ...
Страница 152: ...Chapter 5 7SR158 Installation Guide Chapter 5 Page 4 of 14 2013 Siemens Protection Devices Limited ...
Страница 164: ...Chapter 6 7SR158 Commissioning Maintenance Guide Chapter 6 Page 2 of 24 2013 Siemens Protection Devices Limited ...
Страница 188: ...Chapter 7 7SR158 Applications Guide Chapter 7 Page 2 of 24 2014 Siemens Protection Devices Limited ...
Страница 211: ......