Applications
9.1 Parallel connection to increase the power rating
SITOP PSU6200 3ph
56
Equipment Manual, 02.2020, A5E44623402-1-76
NOTICE
Protective circuit for the parallel connection of more than two power supplies
When connecting more than two power supplies in parallel, additional measures must be
taken to prevent high reverse currents in the event of a secondary device fault. For this
purpose, a suitable protective circuit (e.g. decoupling diode or DC-capable circuit breaker)
must be installed between each "+" terminal of the power supply and the common
connection point.