Technical data
6.7 Mechanical system
SITOP PSU6200 3ph
46
Equipment Manual, 02.2020, A5E44623402-1-76
6.7
Mechanical system
6EP3433-7SB00-0AX0
(24 V/5 A)
6EP3434-7SB00-3AX0
(24 V/10 A)
6EP3436-7SB00-3AX0
(24 V/20 A)
Connection system
Spring-loaded terminal
Connections: Line input
L1, L2, L3, PE: 1 spring-loaded terminal each for 0.2 - 6 mm²
solid/finely stranded
L1, L2, L3, PE: 1 spring-
loaded terminal each for
0.2 - 10 mm² solid/finely
stranded
Connections: Output
+, -: 2 spring-loaded terminals for "+" and 3 spring-loaded
terminals for "-" for 0.2 - 4 mm² solid and 0.2 - 2.5 mm² finely
stranded
+, -: 2 spring-loaded terminals
for "+" and 3 spring-loaded
terminals for "-" for
0.2 - 10 mm² solid/finely
stranded
Connections: Auxiliary
contacts
Signaling contact: 2 spring-loaded terminals for 0.2 ... 1.5 mm² solid/finely stranded
Width of the housing
35 mm
45 mm
70 mm
Height of the housing
135 mm
135 mm
135 mm
Depth of the housing
125 mm
155 mm
155 mm
Installation width
35 mm
45 mm
70 mm
Mounting height
225 mm
225 mm
225 mm
Weight, approx.
0.7 kg
0.9 kg
1.5 kg
Product feature of the
housing: housing that can
be lined up next to one
another
Yes
Type of mounting /
panel mounting
No
Type of mounting:
rail mounting
Yes
Type of mounting:
S7-300 standard rail
mounting
No
Mounting
Can be snapped onto standard TH35-15/7,5 mounting rails (EN 60715)
Содержание 6EP3433-7SB00-0AX0
Страница 8: ...Safety instructions SITOP PSU6200 3ph 8 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 22: ...Mounting removal SITOP PSU6200 3ph 22 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 34: ...Installation 5 2 Output side connection SITOP PSU6200 3ph 34 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 48: ...Technical data 6 8 Dimension drawing SITOP PSU6200 3ph 48 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 54: ...Ambient conditions SITOP PSU6200 3ph 54 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 62: ...Environment SITOP PSU6200 3ph 62 Equipment Manual 02 2020 A5E44623402 1 76 ...