Description, device design, dimension drawing
2.4 Status displays and signaling
SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
13
Device with diagnostics monitor
Figure 2-6
Signaling, signaling contact
Signaling contact
6EP3434-7SB00-3AX0 (24 V/10 A)
6EP3436-7SB00-3AX0 (24 V/20 A)
LED "O.K.":
green:
green flashing (0.5 Hz):
Output voltage U
out
> 20 V or U
out
> 23 V
shutdown as a result of thermal overload
LED "LOAD":
green:
yellow:
reached service life < 90 %
reached service life
≥
90 %; I
out rated
≥
90 %
LEDs above LED "LOAD":
LED 5.1 green:
LEDs 5.1+5.2 green:
LEDs 5.1+5.2+5.3 yellow:
I
out rated
30 - 60 %
I
out rated
60 - 90 %
I
out rated
> 90 %
Contact ''COM'' (13, 14)
closed:
Output voltage U
out
> 20 V or U
out
> 23 V; alternative data transfer (DIP switch COM = 1)
NOTICE: It is not permissible that the contact is connected on the primary side!