Installation
5.2 Output-side connection
SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
33
5.2
Output-side connection
SITOP PSU6200 power supplies provide at their outputs an isolated (= non-grounded) SELV
output voltage (Safety Extra Low Voltage). The output of the power supply is no-load,
overload, and short-circuit proof. If an overload occurs, the electronic current limitation limits
the output current to a maximum value (refer to chapter Technical data (Page 35)).
Figure 5-2
Output-side connection
The output voltage is connected via the "+" and "-" terminals at the output of the power
supply (see Figure Output-side connection (Page 33)). Ensure that the output cables are
dimensioned correctly for the maximum output current rms value and fused accordingly.
The subsequent digit, e.g.: "+1" designates the unique terminal connection, therefore
simplifying correct wiring.
Note
If the safety concept of the plant or system specifies that the DC output circuit should be
grounded (PELV), then it is permissible that the output voltage of the SITOP power supply is
grounded. In this case, ideally, the grounding at the output should be directly connected from
terminal "-" of the power supply to a suitable connection point of the protective conductor
system (PE) of the plant or system.
Содержание 6EP3433-7SB00-0AX0
Страница 8: ...Safety instructions SITOP PSU6200 3ph 8 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 22: ...Mounting removal SITOP PSU6200 3ph 22 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 34: ...Installation 5 2 Output side connection SITOP PSU6200 3ph 34 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 48: ...Technical data 6 8 Dimension drawing SITOP PSU6200 3ph 48 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 54: ...Ambient conditions SITOP PSU6200 3ph 54 Equipment Manual 02 2020 A5E44623402 1 76 ...
Страница 62: ...Environment SITOP PSU6200 3ph 62 Equipment Manual 02 2020 A5E44623402 1 76 ...