SITOP PSU6200 3ph
Equipment Manual, 02.2020, A5E44623402-1-76
21
Mounting/removal
3
WARNING
Installing the device in a housing or a control cabinet
SITOP PSU6200 power supplies are built-in devices. They must be installed in a housing or
control cabinet where only qualified personnel have access.
The device can be mounted in a control cabinet on standard mounting rails according to
TH35-15/7,5 (EN 60715).
Mounting
The device must be mounted in such a way that the input terminals are at the bottom and the
output terminals at the top. A clearance of at least 45 mm must be maintained above and
below the device (max. cable duct depth 50 mm).
Removal
To remove, pull up the slider
⑥
using a screwdriver and disengage the device at the bottom
edge of the standard mounting rail (see Removal diagram (Page 21)). Then you can remove
the device from the upper edge of the standard mounting rail.
Figure 3-1
Mounting/removal