6.2.4
Routing the cable into the terminal box
Normally the cable entry plate is supplied drilled. The number and size of the cable entry tapped
holes is provided in the machine dimension drawing.
Inserting the cable into the terminal box
1. Only use cable entries that are suitable for the cable.
2. Only use suitable cable entries and cables for the prevailing ambient temperature.
3. Ensure that the power cables are strain relieved where they enter the terminal box.
4. Carefully connect the cable and ensure a reliable protective conductor connection.
5. Tighten the glands and the elements for the strain relief with the torque specified by the
manufacturer.
6. Check the cable glands and cables to ensure that they are correctly sealed and firmly
seated.
7. Correctly close and seal threads or holes that are not being used ensuring that the IP degree
of protection is maintained. The IP degree of protection is specified on the rating plate.
Rotating the terminal box
Depending on the particular version, the terminal box can be rotated. It can then be rotated
through increments of 90° corresponding to the connection direction.
If necessary, contact your Service Center (Page 111).
6.2.5
Terminal boxes with type of protection "Ex d/Ex db"
With terminal boxes of protection type "Ex d" or "Ex db", the type and size of the cable entry
threads and the type of protection are stated on the terminal box.
● The cable entries must be suitable for the cables.
● The cable entries and cables must be suitable for the ambient temperature.
WARNING
Explosion hazard when non-approved components are used
If cable entries, pipe or conduit systems, and filler plugs of a simple design are used with
terminal boxes with type of protection "Ex d" or "Ex db", this can result in an explosion
during operation. This can result in death, serious injury, or material damage.
● Use only filler plugs with type of protection "Ex d/Ex db" that have been tested and
certified in accordance with IEC / EN 60079-1 to plug holes that will not be used.
Electrical connection
6.2 Preparation
SIMOTICS HV C 1NB1402-2AA84-4CA0-Z
Operating Instructions 06/2018
57
Содержание 1NB1402-2AA84-4CA0-Z
Страница 2: ...26 06 2018 15 34 V3 00 ...
Страница 10: ...Table of contents SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 10 Operating Instructions 06 2018 ...
Страница 22: ...Description SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 22 Operating Instructions 06 2018 ...
Страница 84: ...Operation 8 9 Faults SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 84 Operating Instructions 06 2018 ...
Страница 110: ...Disposal 11 4 Disposal of components SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 110 Operating Instructions 06 2018 ...
Страница 112: ...Service and Support SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 112 Operating Instructions 06 2018 ...
Страница 117: ...117 ...
Страница 118: ...118 ...
Страница 119: ...119 ...
Страница 120: ...120 ...
Страница 121: ...121 ...
Страница 122: ...122 ...
Страница 123: ...123 ...
Страница 124: ...124 ...
Страница 125: ...125 ...
Страница 126: ...126 ...
Страница 127: ...127 ...
Страница 128: ...128 ...
Страница 129: ...129 ...
Страница 130: ...130 ...
Страница 131: ...C 2 Declaration of conformity SIMOTICS HV C 1NB1402 2AA84 4CA0 Z Operating Instructions 06 2018 131 ...
Страница 132: ...Quality documents C 2 Declaration of conformity SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 132 Operating Instructions 06 2018 ...
Страница 133: ...133 ...
Страница 148: ...148 ...
Страница 150: ...Additional documents SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 150 Operating Instructions 06 2018 ...
Страница 154: ...Index SIMOTICS HV C 1NB1402 2AA84 4CA0 Z 154 Operating Instructions 06 2018 ...
Страница 155: ...AF Einbauerklärung Loher LDX U157 AJ EC Declaration of Conformity U161 ...