8. Bring the drive system into operation in accordance with the operating manual for the
converter or inverse rectifier.
9. Ensure that the maximum permissible speed n
max
is not exceeded (see type plate for
details). The maximum permissible speed is the highest permissible, short-term
operating speed.
10. The fitted temperature sensor cannot cater for all possible faults (note the instructions
in the project planning guide).
7
Instructions in case of faults
In case of deviation from normal operation or faults, proceed first according
to the following list:
Contact the works, please also refer to the relevant section of the operating manual for the
components of the entire drive system.
Do not disable the protective devices, even in trial operation.
Consult the manufacturer or the SIEMENS service center when necessary.
For start up, system motor converter:
A&D Hotline 0180 50 50 222
For motor / motor components:
Contact in the works 0174-3110669
Fault
Cause
Remedy
Irregular running
Inadequate screening of the
motor or encoder cables.
Check screening and grounding (see
section 5.1)
Amplification of the drive control-
ler too high
Adjust controller (see converter operat-
ing manual)
Vibrations
Coupling elements or driven
machine are badly balanced
Rebalance
Inadequate alignment of the drive
train
Realign the machine set
Fixing screws are loose
Check and tighten screw connections
Running noises
Foreign bodies inside the motor
Repair by the manufacturer
Bearing damage
Repair by the manufacturer
Motor overheats
(Surface temperature
>140 °C)
Temperature monitoring
responds
Drive overloaded
Check load (see type plate)
Heat dissipation impaired by
deposits
Clean surface of drives.
Ensure that the cooling air can flow
freely in and out