IV431E REV. 00 Issued: 2020/11/16 User Manual Soleil SPX 200K-250K
Pag. 43 of 76 +FR
The torque used to tighten the external forced cable fixing head of AC wiring is about 15~19N·m.
In order to avoid excessive stress on the cable, the AC cable needs to enter the inverter vertically, and
the external length of the straight section should be not less than 200mm, as shown in Figure3-33.
Figure3-33
AC cable entry requirements (unit: mm)
l
When leaving the factory, outlet end of the cable seal ring is in a sealed status. Before connecting,
puncture it by tool.
l
Please connect the AC output wire according to the relevant requirements of different countries.
Step 3
Tighten the externally forced cable fixing head of the AC terminal clockwise, using a fireproof mud
cable gap.