IV404E Rev.000 SIEL S.p.A.
Issue date: 2017-06-05 Pag. 64 di 90 + FR
J1
J2
J3
SW1
J1
J2
J3
SW1
LED
LED
- RJ45-flat-adapter signals parallel card.
N.B.:
the SAFEPOWER EVO HFT may be provided with two versions of parallel card that differ in the type
of switch used (type 1 or type 2). The difference between the two switches is the position of the control
lever.
Type 1
type 2
LED side
connector side
J1 RJ45 type connector
J2 RJ45 type connector
SW1
start position
connector side(type 1)
LED side (type 2)
Cont
position
LED side (type 1)
connector side (type 2)
LED on
SW1 start position
off
SW1 Cont position
Firmware update
All the parallel-connected UPSs must have the same firmware version. Press key 7 from the
basic menu on the display panel to display the firmware version installed.
For the expansion of an existing system, check that the system has the same firmware version
as the new SAFEPOWER EVO HFT.
Using the cable with two RJ45 terminals provided with each UPS (
A
), make the connections as shown
below: