IV404E Rev.000 SIEL S.p.A.
Issue date: 2017-06-05 Pag. 33 di 90 + FR
3.3.2 SLOTS 2-1 , the following cards may be inserted (optional):
NetMan 102 Plus
(on SLOT 1 main or SLOT 2
aux)
Device for the management of the UPSs on the
Ethernet. It can send information on the status of
the device with various protocols:
TCP/IP UDP (compatible with Watch&Save);
SNMP (for communications with NMS or with PowerNETGuard);
HTTP (to display the status with a browser);
TFTP (to configure or update the device when connected to the network).
The main function of this device is to integrate the SAFEPOWER EVO HFT into the LAN network ensuring a
high level of reliability of communication with the server to enable full management and control of the
SAFEPOWER EVO HFT.
- MULTICOM card (on SLOT 1 main or SLOT 2 aux )
This device may be used to:
-
add a serial port to the UPS;
-
monitor the UPS using MODBUS/JBUS protocol on RS485 or PROFIBUS (Multicom 401)
N.B. each card connected precludes the use of a standard RS232 port, as follows.
the use of SLOT 2 (aux) inhibits the use of RS232-2
For the full and updated list of communication accessories, please see the website www.ups-
technet.com.
3.3.3 REMOTE ALARMS (2 optional cards)
6 outputs: potential-free contacts for alarms (programmable from the display panel), 2 inputs
(programmable from the panel) and 1 12V DC maximum 100mA auxiliary input.