IV404E Rev.000 SIEL S.p.A.
Issue date: 2017-06-05 Pag. 46 di 90 + FR
3.6
Personalizations
Using the CONTROLS PANEL (from the basic menu press keys 3 and 5 and the access code 436215), the
following factory-set electrical parameters can be modified within a certain field:
-
Language,
-
value of the RATED VOLTAGE OUTPUT,
-
BATTERY parameters,
-
end of battery discharge pre-alarm,
-
shutdown due to power lower than a set value,
-
daily programmed shutdown,
-
acceptance frequency and voltage field on the BY-PASS line,
-
by-pass frequency field,
-
modem configuration,
-
RS232-1 and RS232-2 ports.
-
standby-on operation,
-
Smart active operation,
-
date and time.
3.7
Procedure to transfer the load from UPS onto maintenance by-pass.
Procedure not applicable in the frequency converter
With several SAFEPOWER EVO HFTs connected in parallel, follow the procedure described in
the section on
“bypass
for maintenance
”
of chapter
“
Parallel version
”.
The sequences of operations to be carried out to place the UPS in maintenance bypass are shown below.
The procedure varies depending on the initial state of the UPS.