3.8
UPS and load shutdown
This operation will cause the shutdown of the load connected on the output. In parallel versions each
procedure must be carried out on all the UPSs:
open the switch of the load;
open SWOUT, output disconnector;
open SWIN, input disconnector;
open SWBY, by-pass line disconnector;
open the battery cabinet switch/fuse.
The load is no longer powered, and after a few seconds the signal panel will also shut down.
Use a multimeter to check that no voltages are present on the terminal board.
Follow the instructions in the section on START-UP PROCEDURES (see page 38) to restart the UPS.