Protect the device against mechanical damage! Ensure that single shock loads do
not exceed 40 m/s
2
.
▸
Protect the device against dirt and humidity.
Make sure that
dust plugs are plugged on optical fiber connectors equipped
with them during transport of the device
. Otherwise, recommissioning is poten-
tially not possible.
▸
Never touch electronic components.
The following climatic conditions apply to the storage. If required, appropriate measures
must be taken to ensure these climatic conditions (installation of heating/air conditioning
systems etc.):
▸
The storage area must be clean (dust-free, if possible), dry and well-ventilated.
▸
No storage in the open.
▸
The storage temperature must be in the range of −25 °C to +55 °C (−13 °F to
+131 °F). Shortly it may be +70 °C (+158 °F).
▸
The relative humidity on the storage premises must be in the range of 5 % to 75 %
(no bedewing).
▸
Sudden changes of the temperature or the humidity should be prevented.
▸
Avoid stacking of the devices during transport and storage.
The maximum storage period is 2 years. Electrolytic capacitors produce high leakage
currents when a voltage is applied after a long storage period without applied voltage
and must be reformed. For this, the operating voltage is applied via a 1 kΩ series resistor
for one hour. Please contact the SIEB & MEYER service department for details.
2.6
Installation
NOTICE
Damage of electrostatically sensitive components due to improper handling
→ Never touch electronic components..
Note
Consider specific mounting instructions for your device.
Operating conditions:
The following requirements are to be considered for the installation and the operation of
the device. Noncompliance with theses requirements is regarded as
abnormal operat-
ing condition
:
▸
The device is conceived according to DIN EN 61800-1/ DIN EN 50178for the dirt
level 2. That means: Ensure to avoid conductive impurities during the operation.
▸
Devices with air cooling only can be loaded to their maximum up to a height of
1000 m above MSL (3281 ft above MSL). For an operation in areas higher than
1000 m (3281 ft) above MSL the capacity must be reduced by 1.5 % per 100 m
(328 ft).
▸
The device must be protected against harmful gas, oil vapor and salty air at the
place of installation.
▸
The ambient air must not contain aggressive, grinding, electrically conductive or
flammable substances as well as any amount of dust.
▸
The maximum relative humidity during operation is 85 % (no condensation).
9
Gateway 0362151 - PROFIBUS to SERVOLINK 4 Connection
Safety Instructions