Connectors, Switches and Displays
LED
Color
Status
Meaning
Reaction
Red/
green
Flashes
There are not all the SL4 de-
vices available that have been
parameterized on the field-
bus side. Anyhow, the data ex-
change is performed with the
available modules.
None
Green
On
The data exchange is per-
formed with all SL4 devices.
None
Green
Flashes
There are more SL4 devices
available than have been para-
meterized on the fieldbus side.
Anyhow, the data exchange is
performed with the available
modules.
None
Red
Flashes
CRC error
Send the gateway to
SIEB & MEYER.
STA2
Red
On
SL4 interrupted or CRC error in
all SL4 devices
Send the gateway to
SIEB & MEYER.
6.3.2
7-segment Display
The 7-segment display on the front panel shows
status and error messages as code. The three-dig-
it error codes are displayed as sequence.
6.3.2.1
Status Messages
Code
Description
0
OK
6.3.2.2
Error Messages
Code
Description
Course of action
E.03.
Fieldbus module has the internal status "error".
In addition, the LED "SYS" lights red.
Check fieldbus connection.
Restart the gateway.
E.04.
SERVOLINK checksum error
In addition the LED "STA1" is on or flashes (red).
Check the SERVOLINK connection.
Restart the gateway.
E.05.
The heartbeat bit in the SERVOLINK actual value
telegram of one or more drives was not toggled.
Check the drive(s).
Check fieldbus connection.
E.08.
SERVOLINK is not active.
Check the SERVOLINK connection.
Restart the gateway.
E.09.
Fieldbus module was not detected.
Check fieldbus connection.
Check the PLC software.
E.10.
PLC sends zero data telegrams.
Check fieldbus connection.
Check the PLC software.
E.11.
Hilscher COM module: Warm boot was not execut-
ed.
Check fieldbus connection.
Check the PLC software.
E.12.
Hilscher COM module: Cold boot was not executed. Check fieldbus connection.
Check the PLC software.
E.13.
Hilscher COM module No "ready" signal after warm
boot
Check fieldbus connection.
Check the PLC software.
24
Gateway 0362151 - PROFIBUS to SERVOLINK 4 Connection