Safety Instructions
▸
The allowed ambient temperature for the operation is +5 °C to +40 °C (+41 °F to
+104 °F). Extreme and sudden changes of the temperature should be prevented.
– For devices that can be operated in ambient temperatures above +40 °C
(+104 °F) (see technical data), you must consider a reduced service life due to
increased wear of the components.
– Devices with polyester films: The polyester films must not be exposed to direct
sunlight for extended periods of time. In conditions of high humidity (>80 %) the
ambient temperature must not 40 °C (+104 °F). The polyester films
must not come in contact with benzyl alcohol or methylene chloride.
▸
Make sure that the aeration elements are free and open, so that the air circulation
is not restricted.
2.7
Electrical Connection
DANGER
Risk of serious injuries due to touch voltages
After electric devices have been switched off touch voltages may occur de-
pending on the device up to 4 minutes. Longer construction-related dis-
charge times are possible. Refer to the product documentation of your de-
vice.
→ All work at and within the units must only be carried out, when the
units are turned off, the mains supply is cut and the DC bus is com-
pletely discharged.
→ Never touch energized parts after a device has been switched. off.
→ Consider the VDE regulations and the applicable accident prevention
regulations (e.g. VBG 1 and VBG 4).
DANGER
Risk of serious injuries due to improper connection to earth
Incorrect or insufficient connection of the system to earth may cause dan-
gerous currents.
→ Connection to earth must be realized according to the instructions in
the product documentation of your device.
The electrical installation must be carried out according to the relevant electrical codes
(e.g. appropriate wire gauges, fuse protection and connections of ground conductors
must be considered).
Note
SIEB & MEYERdevices are conceived for connection to symmetrically grounded TN
networks. For detailed information regading the connection to TN networks or other net-
works refer to the manual "EMC Guidelines", chapter "Connection to Different Supply
System Types".
Recommendations for the installation complying EMC (e.g. shields, connection to earth
and line installations) can be found in the technical manuals of your device (only for ma-
chine manufacturers). The manufacturer of the system or machine has to meet the re-
quirements of the legislation regarding the EMC.
1. Consider that the mains supply must be protected via an overload release with re-
stricted guidance for each mains phase. The mains line should not be switched on,
before the work is completed.
10
Gateway 0362151 - PROFIBUS to SERVOLINK 4 Connection