The LED STA1 indicates the status of the gateway.
LED
Color
Status
Meaning
Reaction
STA1
Red
Flashes
Start of firmware
Wait until the LED stops
flashing.
Red/
green
Flashes
No communication with the
fieldbus.
Establish the connection to the
fieldbus.
Green
Flashes
The parameters of the fieldbus
are loaded.
None
Green
On
Data exchange
None
Red
On
Internal error
Send the gateway to
SIEB & MEYER.
The LED STA2 indicates the status of the SERVOLINK 4 connection.
LED
Color
Status
Meaning
Reaction
STA2
Red/
green
Flashes
There are not all the SL4
devices available that have been
parameterized on the fieldbus
side. Anyhow, the data
exchange is performed with the
available modules.
None
Green
On
The data exchange is performed
with all SL4 devices.
None
Green
Flashes
There are more SL4 devices
available than have been para‐
meterized on the fieldbus side.
Anyhow, the data exchange is
performed with the available
modules.
None
Red
Flashes
CRC error
Send the gateway to
SIEB & MEYER.
Red
On
SL4 interrupted or CRC error in
all SL4 devices
Send the gateway to
SIEB & MEYER.
6.3.2
7-segment Display
The 7-segment display on the front panel shows
status, error and information messages as
code. The three-digit error and information
codes are displayed as sequence.
6.3.2.1
Status Messages
Code
Description
0
OK
c
Operating mode configuration: Select drives
c.
Operating mode configuration: Save selection
6.3.2.2
Information Messages
Code
Description
H.01.
Speed zero monitoring has detected motor standstill.
W
Connectors, Switches and Displays
Gateway 0362151A - PROFIBUS to SERVOLINK 4 Safety
37
6
Содержание 036215
Страница 1: ...Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety P TD 0000331 12 2019 04 09 SIEB MEYER W ...
Страница 4: ...Chapter Overview W 4 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety ...
Страница 16: ...Safety Instructions W 16 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 2 ...
Страница 18: ...Unit Assembly Complying EMC W 18 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 3 ...
Страница 26: ...Gateway 0362151A W 26 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 4 ...
Страница 28: ...Mounting and Demounting W 28 Gateway 0362151A PROFIBUS to SERVOLINK 4 Safety 5 ...