COMMISSIONING
Fig. 22: Horizontal sensor alignment
Fine adjustment of vertical alignment
1
Slightly loosen the angle bracket screws.
2
Using a small plastic or rubber hammer, very carefully tap the position shown below (
Fig. “Vertical sensor alignment”, page 34
3
Tap until the
VIS Y value
on the display reaches <0.15.
4
Tighten the angle bracket screws again.
Fig. 23: Vertical sensor alignment
1
Retaining screws
2
Angle bracket screws
The LED grid in the visor of the sender/receiver unit shows the position of the light
beam in relation to the reflector center. After fine adjustment, one of the 3 x 3 LEDs in
the center of the grid should light.
If a LED outside the 3 x 3 LEDs in the center lights, fine adjustment must be performed
again.