Configurable functions
4.5.1
Teach-in key-operated switch for C 4000
You can configure an input for a teach-in key-operated switch of the C 4000
Standard/Advanced. Using the teach-in key-operated switch, teach-in of the connected C
4000 is initiated via EFI. Only actuation of the reset button connected to the C 4000
causes the new configuration to be received in the C 4000.
$
The teach-in key-operated switch connected to the UE 440/470 affects all C 4000s
connected via EFI.
$
You must use an N/O contact for the teach-in key-operated switch; the input is active
HIGH.
You configure whether an input delay is necessary for a teach-in key-operated switch (see
Page 52).
Context menu device symbol UE 440/470, command
Edit configuration draft…
in Edit
configuration draft
window, context menu element symbol
teach-in key-operated switch
for C 4000
, command
Element wizard…
.
The electrical connection of the teach-in key-operated switch is described in Chapter 6
"Electrical installation" on Page 45.
4.6
Settings for overlapping functions
4.6.1
Complementary or equivalent input evaluation
Complementary evaluation
For proper switching, one channel must always be wired in reverse in comparison to the
others. The following table shows the permissible input levels of both channels.
Channel 1
Channel 2
Logical status
0
0
Error
0
1
1
1
0
0
1
1
Error
Equivalent evaluation
For proper switching, one channel must always be wired the same in comparison to the
others. The following table shows the permissible input levels of both channels.
Channel 1
Channel 2
Logical status
0
0
0
0
1
Error
1
0
Error
1
1
1
Context menu device symbol UE 440/470, command
Edit configuration draft…
in Edit
configuration draft
window, context menu element symbol of the sensor, command
Element wizard…
,
Layout
tab.
Notes
!
Tab. 12: Complementary
evaluation
Tab. 13: Equivalent