Table 3: Modules of the safety controller
Module 1
Main module FX3-CPUx
Module 2
I/O module FX3-XTIO
Module 3 (optional)
I/O module FX3-XTDI
Module 2: Input configuration for FX3-XTIO module
Table 4: Function of the connections
Connection
Function
l1/l2
B100.1 Type 4 electro-sensitive protective device
l3
B100.2 Muting function request
l4
B100.2 Time extension
l5
S300 Pushbutton for the reset function
l6
S200 Hold to run device (connected to test output X2)
Module 2: Output configuration for FX3-XTIO module
Table 5: Function of the connections
Connection
Function
Q1/Q2
Q100 Safety release
Q3
P100 Safe Entry Exit Status
Q4
P101 Hold to run device status
X2
Test output for supply of S200 hold to run device
Module 3: Input configuration for FX3-XTDI module
This module is optional and is only required if timings need to be set for different con‐
veyor speeds or different material sizes.
Table 6: Function of the connections
Connection
Function
l1
S301.1 Timing 1
l2
S301.2 Timing 2
l3
S301.3 Timing 3
l4
S301.4 Timing 4
6.3
Interfaces and signals
Signals for triggering the muting function
This safety system requires two digital 24 V signals from a higher-level control to trigger
the muting function. These signals are part of the initiation sequence for the muting
function.
The first signal for requesting the muting function, MR (Muting Request – in the Flexi
Soft project file also: PLC_Request), detects approaching material with a rising edge
and remains at logical high while an interruption of the Type 4 electro-sensitive protec‐
tive device is expected.
The second signal, TE (Time Extension), changes its status in the opposite direction
from the MR signal.