OVERVIEW OF PARAMETERS
Parameter
Description
QATYP
Output signal settings
• 4 mA ... 20 mA
• 0 V ... +10 V
• Auto V = Qa operated with voltage output of 0 V ... +10 V
• Auto A = Qa operated with current output of
4 mA ... 20 mA
•
Auto? = Automatic signal detection based on the exist
-
ing load resistance
During a menu query, either 4 mA ... 20 mA or
0 V ... +10 V is displayed.
QAFAIL
Output behavior as per NE43 in the event of a fault (func-
tion only available when current output has been selected
under QATYP).
• 3.5 mA = Analog current output is set to 3.5 mA in the
event of a fault.
• 21.5 mA = Analog current output is set to 21.5 mA in
the event of a fault.
SimCur
“8.4.6 Testing the configuration”.
SimVol
“8.4.6 Testing the configuration”.
DspVal
Display settings
• Distan = The display shows the distance in mm in rela-
tion to the end of the probe.
•
QaPerc = The display shows the fill level in % in relation
to the QA analog output with the corresponding QAHIGH
and QALOW thresholds.
• QaBarG = The display shows a bar graph in relation to
the QA analog output with the corresponding QAHIGH
and QALOW thresholds.
• QaSign = The display shows the current QA output value
in mA or V.
• QxSign = The display shows the output states.
Filter
“8.4.2 Filtering measured values”.
SimLev
“8.4.6 Testing the configuration”.
RstFac
Reset the set parameters to the factory settings.
EXPRT
Lock
“8.4.11 Activating the display lock”.
Unit
“8.4.12 Selecting the display unit (millimeter / inch)”.
Offset
Mode