17
Annex
17.1
Checklist for initial commissioning and commissioning
This checklist should be retained and kept with the machine documentation to serve as
reference during recurring thorough checks.
This checklist is not a substitute for initial commissioning or periodic thorough checks
by qualified safety personnel.
17.1.1
Thorough check of the requirements specified in the operating instructions for the safety system
Ambient conditions
Table 75: Ambient conditions
Check sequence
Expected result
Result OK?
1.
Check the ambient conditions.
Compliance with the requirements
specified in the operating instructions
for the safety system is confirmed.
The Flexi Soft system is in an environ‐
ment corresponding to enclosure rating
IP54 (EN 60529) (e.g., inside a control
cabinet).
Yes
⃞
No
⃞
Mounting
Table 76: Mounting requirements
Check sequence
Expected result
Result OK?
1.
Check that the sensor system
has been mounted correctly in
terms of positioning and distance
from bar code tape.
2.
Check that the sensor system
and bar code tape are parallel to
one another.
3.
Check the mounting conditions of
the Flexi Soft safety controller.
Compliance with the requirements
specified in the operating instructions
for the safety system is confirmed.
Yes
⃞
No
⃞
Electrical installation
Table 77: Requirements for the electrical wiring
Check sequence
Expected result
Result OK?
1.
Check the electrical wiring,
including the length of the
cables.
2.
Check that the requirements for
electrical protection and current
limit have been met.
Compliance with the requirements
specified in the operating instructions
for the safety system is confirmed.
An X-junction must be used to connect
the OLM sensors in all cases.
Yes
⃞
No
⃞
Table 78: Electrical requirements for the plausibility signals from the process channel
Check sequence
Expected result
Result OK?
1.
Check that the plausibility signals
from the process controller are
electrically compatible with the
safe inputs of the Flexi Soft
safety controller (refer to the data
sheet).
The electrical data for the plausibility
signals confirms compatibility with the
electrical data for the safe inputs that
are outlined in the operating instruc‐
tions for the Flexi Soft hardware.
Yes
⃞
No
⃞
17
ANNEX
86
O P E R A T I N G I N S T R U C T I O N S | Safe Linear Positioning
8020941/12O9/2019-08-05 | SICK