FLOWSIC200 · Operating Instructions · 8013271/1CJ9/V2-0/2022-01 · © SICK Engineering GmbH
Assembly and installation
3.2.2.2
Bus addressing via hardware setting
The bus address of a sender/receiver unit required for the bus system can be assigned by
hardware or software (
). Hardware addressing is read in when SOPAS ET
starts (
) and has a higher priority than software addressing.
Bus address and sensor number in the MCU are always identical.
As standard, the address is set using a miniature switch on the digital board in the sender/
receiver unit (3 switches for hexadecimal addressing from address 1 to 7;
change the address, open the sender/receiver unit and set the desired address. Then close
the sender/receiver unit again.
Fig. 16
Hardware addressing of sender/receiver unit
NOTICE:
For bus systems, it must be ensured that the bus addressing of the Master
FLSE200 is set correctly.
The sender/receiver units must have different addresses. Identical addresses
for several units cause the communication with the MCU to abort!
Digital board
Miniature switch
Switch 4 serves for Master -
Slave switch-over
Address 1
2
3
4
5
6
7
Switch
1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3
ON
x
x
x x
x x
x
x x x x x
Switch
1
2
3
4
Position
OFF
ON
(Switch position for address 1/Master)
1
2
3
4
Position
OFF
ON
1
2
3
4
(No addressing/Slave)
Содержание FLOWSIC200
Страница 1: ...O PERATING INSTRU CTIO NS FLOWSIC200 Flow Velocity Monitor Installation Operation Maintenance...
Страница 30: ...30 FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH Product description...
Страница 100: ...100 FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH Commissioning and parameterization...
Страница 104: ...104 FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH Maintenance...
Страница 121: ...Specification FLOWSIC200 Operating Instructions 8013271 1CJ9 V2 0 2022 01 SICK Engineering GmbH 121...