Function
Configuration when delivered
Restart interlock
Not configured
External device monitoring (EDM)
Not configured
Cascading
Single system
Smart presence detection
Not configured
Reduced resolution
Not configured
Muting
Not configured
Partial blanking
Not configured
Smart Box Detection
Not configured
Scanning range adjustment
Automatic calibration of the protective field
width
Complementary information
The device must be reset to the factory settings to change the configuration to the
following functions:
•
External device monitoring (EDM)
•
Restart interlock
•
Cascading
All other functions can be changed subsequently without resetting the safety light
curtain to factory settings.
Further topics
•
"Reset to factory settings", page 94
7.3.1
Reset to factory settings
Overview
The sender and receiver are reset to factory settings independently of each other. The
procedure is the same for the sender and receiver.
The following functions must be reset to factory settings following a certain proce‐
dure:
•
External device monitoring (EDM)
•
Restart interlock
•
Cascading
The device must also be reset to the factory settings if the device has previously used
the functions of the SP2 system plug and is now to be operated with an SP1 system
plug.
All other functions will be reset to the factory settings by setting the DIP switches to Off.
1
O
N
2
OFF
uncoded
code 1
code 2
rev.conf.
ON
1
O
N
2
D
Figure 56: Reset to factory settings
7
CONFIGURATION
94
O P E R A T I N G I N S T R U C T I O N S | deTec4
8021645/1EB0/2022-04-28 | SICK