16
DST2600 User’s Manual
If the engine is in a transitory phase (starting, stopping, cooling, that is the engine is not neither
in running nor in stopped status) the first row alternates the visualization of the electrical
measurements seen above with the description of the present engine status. The possible
indications are:
"
STOP CYCLE
": the engine is stopping.
"
ABORT STOP
": the stop cycle is interrupted for a new start request.
"
ENG. NOT STOPPED
": the engine is not stopped after a stop cycle.
"
PREHEAT
": it is active the glow plugs command foe Diesel engines, awaiting the real
start.
"
FUEL SOLENOID ON
": th
e “FUEL” command is active but the “START” command
not yet.
"
CRANK IN PROGR.
": the “START” command (engine starter) is active for the engine
crank.
"
DELAY
": one crank attempt was not successful and it is in progress the pause before
next attempt.
"
CHECK FOR RUN
": the “START” key, in MAN mode, has been released before the
engine was really running; the device waits some seconds to check if the engine really
starts or it dies.
"
WAIT FULL SPEED
": the engine is running; the devices is waiting that the generator
electrical measurements reach their proper tolerance thresholds.
"
COOLING
": cooling cycle in progress
"
CLEANING
": washing cycle in progress.
"
WAITING FOR STOP
": stop cycle in progress, excitation engine stop time elapsed.
"
IDLE SPEED.
": the engine is running but it is active the idle speed command.
With these visualizations, keep pressed the “AUX/PROGRAM” key to hide the engine status
and to show the generator electrical measurements.
Some of the status above described take place only if programmed on
purpose (i.e. “cleaning”
or “idle speed”)
If any anomaly is present, on second row there is the description of the anomaly/anomalies
pending. The description of the anomaly slides on second row; if more than one anomaly is
active, they are visualized cycli
cally. In this situation, keeping the ”AUX/PROGRAM” key
pressed the anomalies are hided and the power measurements return visible.
Only if the device is in “OFF_RESET” mode, press the “AUX/PROGRAM” key to enter in the
parameter programming procedure.
Whatever is the visualization mode, when an anomaly occurs the visualization is forced
to “MODE1”.
In “MODE2”, pressing more time the “AUX/PROGRAM” key, it is possible to visualize four
different pages, containing measurements related to generator and to mains
- Page 1: