background image

 

26     

DST2600 User’s Manual 

 

In the “MAN” mode, loads are usually changed-over to mains. Using the “KM/KG” button it is 
possible  to  invert  the  changeover  status  (the  changeover  to  genset  is  possible  only  if  the 
conditions previously seen are verified). NOTE: it is possible only to invert the status: it is not 
possible  to  leave 

open both the breakers. Passing from “AUTO” to “MAN”, the changeover 

status doesn’t change. 

In “AUTO” mode, the loads are changed-over on genset (with respect of the proper conditions) 
only when mains is out of the tolerance thresholds. As soon as mains comes back in tolerance, 
loads  are  newly  changed-over  on  mains  (with  proper  delay  times,  see  the  sequence  of  the 
mains).  Passing  from  any  other  working  mode  to  “AUTO”,  loads  are  forced  as  described, 
driving  a  changeover  if  needed.  The  “KM/KG”  button  is  ignored.  This  status  uses  another 
timing: to close the loads on genset it must be passed the P.218 time since engine started, or, 
more precisely, since the genset voltages and frequency are internal to their tolerance bands. 
This delay is used mainly to give a minimum time to the engine to warm itself before supply 
the load 

In  the  “TEST”  mode,  loads  are  normally  changed-over  to  mains.  Passing  from  any  other 
working mode to “TEST”, loads maintain their status. Using the “KM/KG” button it is possible 
to invert  the changeover status (the changeover to  genset is possible only  if the  conditions 
previously seen are verified). NOTE: it is possible only to invert the status: it is not possible to 
leave open both the breakers. For this status too the delays configured with P.218 are applied. 
It has to remember that the board passes automatically in AUTO (aborting TEST mode) if its 
automatic intervention is required.  

In “REMOTE START” mode, the loads are always changed-over on genset (with respect of 
the proper conditions). Passing from any other working mode to “REMOTE START”, loads are 
forced as described, driving a changeover if needed. The “KM/KG” button is ignored. P.218 is 
used  in  this  status  too.  It  has  to  remember  that  the  board  passes  automatically  in  AUTO 
(aborting TEST mode) if its automatic intervention is required 

 

 

This function allows to monitorize the trend of the active power in order to diagnose 

a “low” or 

“high” load condition (selectable by P.481 parameter, 0 means “low”, 1 means “high”). The 
low/high status is signaled by a digital output configured as “4  – load function status”: if no 
output is configured in this way, this function is disabled.  

This function may be enabled/disabled with a digital 

input appositively configured (code “33-

load function enabled); if no input is configured with code 33, the function is always enabled. 
If, however, at least one input is configured in this mode, the “low” load survey is enabled after 
P.482 seconds from input activation. 

If  power  drops  down  for  P.484  seconds  under  the  threshold  P.483  the 

“low  load”  status  is 

detected,  if  it  rises  for  P.486  seconds  over  the  threshold  P.485  the 

“high  load”  status  is 

detected; in the other cases the status stays unchanged (histeresys). 

The output is activated when : 

 

“low” load condition is detected if P.481 is set to zero. 

 

“high” load condition is detected if P.481 is set to one. 

 

 

 

 

 

Содержание DST2600

Страница 1: ...Filename EAAM016305EN Rev 05 Date 05 11 2014 ID Document EAAM0163 Product DST2600 ...

Страница 2: ...es and warning alarm lights 9 8 2 3 MAINS LIVE light 9 8 2 4 Generator live engine running light GENERATOR ENGINE 10 8 2 5 Change over status lights KM KG 10 8 3 Key switches 10 8 3 1 Cursor keys arrows UP and DOWN 10 8 3 2 MODE ACK key 12 8 3 3 AUX PROGRAM key 12 8 3 4 Changeover selection KM KG 13 8 3 5 Engine START key 13 8 3 6 Engine STOP key 13 8 4 Multifunctional display 14 8 4 1 Internal di...

Страница 3: ...l start 25 11 10 Automatic start and stop 25 12 CHANGE OVER LOGIC 25 13 LOAD MANAGEMENT 26 14 DST2600 Start up 27 15 PARAMETERS PROGRAMMING 27 15 1 Entering and modifying parameters 27 15 2 Password setting 29 16 ANOMALIES 29 16 1 Forward 29 16 2 Anomalies signalling organization 30 17 TECHNICAL CHARACTERISTICS 30 17 1 Fundamentals 30 17 2 Current absorption 31 17 2 1 Battery current absorption wi...

Страница 4: ...device is powered on the multifunction display will appear for about 3 seconds the following message SICES s r l DST2600 revXX YY In both cases XX is a two digit number the identifies the major software version YY is a two digit number that identifies the minor software version The complete device SW code is EB0220085XXYY or EB0220141XXYY If the software revision is 00 06 or 0 06 the actual code S...

Страница 5: ...ECTRICAL SHOCK THE FRONTAL PANEL REMOVING AND ALL THE OPERATION INSIDE THE PANEL MUST BE CARRIED OUT EXCLUSIVELY BY AUTHORIZED PERSONNEL AND ONLY IF MAINS SOURCE IS DISCONNECTED THE GENSET ENGINE IS NOT RUNNING AND ENGINE STARTING BATTERY DISCONNECTED Safety ground connection is MANDATORY and required for the proper device functionality It must be done before any other connection SICES srl is no i...

Страница 6: ...ase to terminal L1 REMARK the wiring cross section to be used for generator power lines is 16mm2 for 40kVA applications DST2600 is equipped with a charge maintainer that has the purpose of supply the internal logic and compensate the self discharge of the main engine battery It is supplied from phase L1 of the mains line it is thus required that in three phases system the neutral line is connected...

Страница 7: ...ettable fuses work as thermal switch and don t require any operator procedure remove the overload source and wait for protection cooling down Each line input both mains and generator has a protection fuse The fuse type is a 5x20mm 1A and it is used to protect against internal faults Only exceptions fuse F203 on mains phase L1 and F200 on generator phase L1 are 2A fuses The reason is that F203 outp...

Страница 8: ...ts use is not scheduled The upper part of the control panel is made of polycarbonate resistant to oil and solvents which has symbols and identification strings Here there are all the commands the alphanumerical signalling and the warning lights these will be described in details in the following paragraphs The frontal panel can be different in the graphical aspect with respect to the one shown her...

Страница 9: ...NG light also flashes when a warning arises an anomaly that doesn t cause the engine shutdown the MODE 3 ALARM instead flashes when a block or a deactivation has occurred When a new anomaly occurs of any type the display visualizations is forced to MODE 1 allowing the visualization of the description of the anomaly It is however possible to select any other mode also with one or more anomalies pen...

Страница 10: ... tolerance thresholds ON if generator frequency and voltages are steadily between their tolerance thresholds The two lights green show if the loads are supplied by mains KM or by generator KG The device has seven key switches each of them has associated one or more function depending on the context With the UP and DOWN keys it is possible to select the genset working mode OFF_RESET MAN AUTO Each m...

Страница 11: ...is mode the board is ready to manage a manual use of the genset In brief 1 The manual start and stop procedure are enabled where the automatic procedure are disabled so the engine won t never start automatically by the board 2 It is possible to changeover the loads on generator with the explicit command of the operator only if the generator is in the proper condition to supply The changeover won t...

Страница 12: ...he multifunctional display currently selected Press the key to pass to the next window of the mode in a cyclical way If the key is pressed together with the MODE ACK key it allows the manual regulation of the display s contrast level this regulation is available only for some display models and only from software version 00 03 with previous version this keys combinations allows to stop the generat...

Страница 13: ...ep pressed AUX PROGRAM first and then use START each pressure increments the value of 10 units In OFF_RESET press this key to switch on all the LED lights LAMP TEST to diagnose possible failures In MAN mode when pressed the key immediately stops the engine if the load was supplied from generator it is immediately changed over on mains before commanding the engine stopping It is not necessary to ke...

Страница 14: ... The internal lamp is switched on pressing any key its turn off can be configured with the parameter P 492 it is the maximum working time in seconds of the lamp since the last key was pressed Setting the parameter to zero to leave the lamp always on NOTE if the lamp is switched off the pressure of a key causes only the switching on of the lamp and doesn t involve the action predefined for the key ...

Страница 15: ... the phase currently visualized expressed in Amperes It is visualized with two decimal digits if lower than 10 amps otherwise with only one decimal digit If the value is lower than 0 66A for 20kVA version or 1 2A for 40kVA version the visualization is forced to zero Generator frequency in the right side of the first row there is shown the frequency of the generator voltage always related to the L1...

Страница 16: ...ng that the generator electrical measurements reach their proper tolerance thresholds COOLING cooling cycle in progress CLEANING washing cycle in progress WAITING FOR STOP stop cycle in progress excitation engine stop time elapsed IDLE SPEED the engine is running but it is active the idle speed command With these visualizations keep pressed the AUX PROGRAM key to hide the engine status and to show...

Страница 17: ...y its apparent phase power in kVA by its power factor and by the indication of the type of its load i if inductive c if capacitive The second row shows the active power in kW and the reactive power in kvar of that phase If the active power and the power factor have negative sign the system is working in a power reverse situation NOTE if in MODE1 the phases scansion is halted this page will result ...

Страница 18: ...rt battery voltage in volts with one decimal digit The start counter can be reset Page 2 On second row there are visualized three counters related to the engine running hours On the left side there is the total engine running hours absolute hours in the centre the partial engine running hours and on the right side the engine running hours missing before the engine maintenance this function must be...

Страница 19: ...own Inhibition of generator automatic operations requested by digital input Inhibition of generator automatic operations requested by clock REMOTE START mode activated Page 2 On the first row there is shown the total working hour of DST2600 since it was supplied on the second row there is an alphanumerical code with 12 characters unambiguous for each device serial number Page 3 This page shows the...

Страница 20: ...te and time are marked as not valid in some cases this situation causes the activation of a warning signaling Date and time are marked as valid only when you change them or a part of them even if you simply confirm actual values You can change date and time by the serial port SicesSupervisor PC software or manually by the standard parameter programming function the year the month the day etc are n...

Страница 21: ...cedure is changed from revision 00 06 of DST2600 Up to 00 05 version parameters involved are P 419 and P 420 Parameter P 419 is a time expressed in hours it is the time interval between one test and the next This time is computed from the beginning of the previous test the length of the test has not influence over its repetition time The parameter P 420 is a time expressed in minutes and it is the...

Страница 22: ...ined as limit value of their related measurements some other as percentage with respect to a minimal value Following the system implementation or the type of intervention that they have the modality to disable the protections changes it can be necessary to set a particular value in a threshold value or simply to deselect the protection itself In the document EAAM0147xx parameter list there is a co...

Страница 23: ...activate the input o The command can be sent over the serial port or by an SMS In this case the command can be accepted only if one digital input of the board is configured as 29 Remote start enable and this input is activated When the input will be deactivated the DST2600 immediately goes back to AUTO mode even if it has not yet received the reverse command from serial port SMS DST2600 acquires t...

Страница 24: ...essage is shown on the STATUS page of MODE 4 display mode This command can be used to prevent the genset startup for mains faulty The command has no effect in MAN mode and doesn t prevent the starting for TEST and REMOTE START its activation is signaled by the MAINS LIVE light which flashes also with mains presence DST2600 is able to start stop and protect the engine with a series of thresholds up...

Страница 25: ...o ways a With normal procedure This procedure consists of doing an engine cooling cycle only if the load was been connected to the generator keeping it running with no loads connected This procedure is applied if o No more automatic start request is pending mains present and board in AUTO mode o An anomaly qualified as deactivation has occurred it is an anomaly typically dangerous for loads but no...

Страница 26: ... is not possible to leave open both the breakers For this status too the delays configured with P 218 are applied It has to remember that the board passes automatically in AUTO aborting TEST mode if its automatic intervention is required In REMOTE START mode the loads are always changed over on genset with respect of the proper conditions Passing from any other working mode to REMOTE START loads a...

Страница 27: ...tarts to run its working sequences DST2600 has many parameters that allow to adapt its working to many employment situations The access to the programming procedure can be protected by a password set by the system installer The parameters modification must be done exclusively by specialized personnel because an error could compromise the intervention and the working of the genset and also cause da...

Страница 28: ... decreased of ten units at time To confirm and store the new parameter value press the MODE ACK key to abort the modification press and release the AUX PROGRAM key alone in both the cases the square brackets stop flashing modification ended In no way it is possible to enter for a parameter values not acceptable to the device for instance it is not possible to set a negative value for a time it is ...

Страница 29: ...be unlocked For the same reason it is recommended to set immediately a password to avoid that it could be modified by external personnel or inserted for mistake DST2600 has many alphanumerical signalling to highlight the arising of anomalies When an anomaly occurs during the normal working that means in MAN or AUTO not OFF_RESET modes the visualization mode passes automatically to MODE1 whatever i...

Страница 30: ...warning block or deactivation Since the message for the configurable digital input can be customized and moreover some written can be common to many anomalies for example the written for the high coolant temperature is the same for the contact sensor and the analogue sensor what identifies univocally an anomaly is its three digit code When reporting an anomaly besides the description refer its cor...

Страница 31: ...mm HxLxP P 165mm with emergency pushbutton Protection degree IP30 o With engine stopped and display light switched off 150mA 12 6V o With engine stopped and display light switched on 320mA 12 6V o With engine running 440mA 12 5V The current absorption from mains line is fundamentally function of the battery charge status Generally the mean absorption with engine stopped is about 110 130mAac 230Vac...

Страница 32: ...32 DST2600 User s Manual Overall dimensions 460X345X140 mm HxLxP P 165mm with emergency pushbutton DST2600 panel can be hanged up to a wall using the notches on rear side ...

Страница 33: ... the right to modify this document without prior notice SICES has made any effort to ensure that the information herein provide are correct in any case SICES does not assume any liability for the use these information The disclosure by any means of this document to third parties is not allowed ...

Отзывы: