Manual of SR288 intelligent controller
47
FTYP
Flow meter selection
1
1
Flow meter with fixed
flow value
2
Grundfos flow meter
(VFS)
3
Rotary vane flow
meter (FRT)
FMAX
6L/min
0.5-100L/
min
0.1
Flow rate enter
MEDT
3
0-3
Medium type
0: water
1: Propylene glycol
2: Ethylene glycol
3: Tyfocol LS/G-LS;
MED%
45%
20-70%
1%
Concentration
of
medium
Function setting
►Select OHQM menu
►Press “SET”, “OHQM OFF” displays on the screen
►Press “SET”, “OFF” blinks
►Press “▲/▼”, to activate this function, “OHQM ON” displays on the screen
►Press “SET” or “ESC” to save the setting
►Press “▲”, “FTYP 1” displays
►Press “SET”, “1” blinks
►Press “▲/▼”, select type of the flow meter (1, 2, and 3)
►Press “SET” or “ESC” to save the setting
►Press “▲”, “FMAX 6” displays on the screen
►Press “SET”, “6” blinks
►Press “▲/▼”, to adjust flow rate
►Press “SET” or “ESC” to save the setting
►Press “▲”, “MEDT 3” displays on the screen
►Press “SET”, “3” blinks
►Press “▲/▼”, to select medium type
►Press “SET” or “ESC” to save the setting
►Press “▲”, “MED% 45” displays on the screen
►Press “SET”, “45” blinks
►Press “▲/▼”, to adjust the concentration of medium